9 Control ___________________ 39 3 Design of the indoor unit _______ 8 Menu 1 - INDOOR CLIMATE ________________ 39 HM 6Split / HM 12Split ___________________ 8 Menu 2 - HOT WATER ____________________ 40 Dimensions and pipe connections ___________ 10 Menu 3 - INFO _________________________ 40...
This appliance can be used by Marking children aged 8 years and above HM 6Split / HM 12Split is CE marked and persons with reduced phys- and has an IP21 protection rating. ical, sensory or mental capacity...
Page 5
Connecting communication Perimeter protection Protection, indoor unit Building protection Outdoor temperature sensor Room sensor Current sensor Safety circuit breaker Residual-current device Setting the thermostat to emer- gency mode Miscellaneous Docked to HM 6Split Section 1 | Important information HM 12Split...
• HM 6Split - unit dedicated for use with L 6Split. CAUTION The HM 6Split / HM 12Split unit must be hanged on • HM 12Split - unit dedicated for use with L 8Split the wall using the included hanger. The device can be and L 12Split.
Installation location Supplied components HM 6Split / HM 12Split can be installed in any room • Hanger (1 pc.) protected against temperature drop below 0°C to • Safety group (1 pc.) avoid freezing of the heating medium. 800 mm of •...
3 Design of the indoor unit HM 6Split / HM 12Split XL11 AA23 AA2:X4 BT30 K1A-K3A AA27 AA2:X15 AA2:X4 XL10 XL13 XL14 BT12 BT63 BT25 BT71 BT15 QN10 GP12 Section 3 | Design of the indoor unit HM 6Split HM 12Split...
Page 9
Rear left cable groomet Rear right cable groomet Lower left cable groomet Lower right cable groomet Nameplate Plate with the designation of the hydraulic connections Serial number Software serial number HM 6Split Section 3 | Design of the indoor unit HM 12Split...
XL13 XL14 Pipe connections Connection, heating medium supply, Ø22 mm for HM 6Split and HM 12Split, Connection, heating medium return, Ø22 mm for HM 6Split and HM 12Split, Connection, HW heating medium supply, Ø22 mm for HM 6Split and HM 12Split, XL10 Connection, GW1/2”...
5 m. The HM 6Split / HM 12Split unit can be docked to the central heating, cooling operation and hot water sys- tems. It is absolutely necessary to install the safety assembly on connection XL11.
Page 12
The term “climate system” which is used in this instal- lation and user manual signifies heating and cooling operation systems that are supplied with heat or cold using heating or cooling medium from the HM 6Split / HM 12Split unit, for heating or cooling purposes. Zbiornik buforowy The heat pump installation requires an appropriate volume of heating medium (approx.
• All required safety devices and shut-off valves be connected to the WM1 stud. This enables draining must be fitted as close to the HM 6Split / HM off all condensate away from the device, minimising 12Split unit as possible.
Page 14
• The connection of refrigerant pipes to the out- specification door unit and the indoor unit should be made with flared connections after removing the pro- HM 6Split duction ends. • Make and connect the flare-connection and tighten HM 6Split Gas pipe (Ø...
Page 15
(QM35, QM36) CAUTION closed. In order to fill the pipes of HM 6Split / HM The pipe connection between the indoor unit and the 12Split with refrigerant, they must be reopened.
Page 16
Maximum pressure, climate system 0,3 MPa (3 Bar) Highest recommended flow/return temperature at dimensioned 55/45°C outdoor temperature. Max. temperature in the unit HM 6Split / HM 12Split +70°C Maximum hot water temperature +60°C Minimum temperature ext. operation of the unit -20°C...
The location of the sensors is shown in the domestic hot water connection diagram. DHW tank The HM 6Split / HM 12Split unit is not equipped with should be connected to a water system with a water a shut-off valve for the central heating system, it must pressure recommended by the tank manufacturer.
Page 18
4-pipe system can be found in the SERVICE stalled on an external supply pipeline at a distance section, menu 5.2.4. of min. 1 m from HM 6Split / HM 12Split along the pipeline. However, in the case of a system equipped SHB10...
External temperatures down to -20 ° C. The connection of the outdoor unit, hot water tank and the indoor unit HM 6Split / HM 12Split, with a system of pipes filled with refrigerant, protects the GP11 connection against freezing in the event of interrup- tions in the electric power supply to appliances.
“heavy side” and two people are required to set the L Split in position. Do not place the L Split heat pump directly on the lawn or other unstable surface. Section 5 | L Split outdoor unit HM 6Split HM 12Split...
Use a siphon for installations where air circula- tion may occur in the condensation water drain- age pipe. • The insulation must be tightly fitted to the bot- tom of the condensation water trough. HM 6Split Section 5 | L Split outdoor unit HM 12Split...
Page 24
The installation length can be adjusted by the size of the siphon. NOTE If none of the recommended options will be used, proper drainage of condensate must be ensured. HM 6Split Section 5 | L Split outdoor unit HM 12Split...
L 6Split L 8Split L 12Split Sound power levels, according to EN12102 at 7/35°C (rated value)* Sound power level at a distance of 2m (rated value)* dB(A) *Free space HM 6Split Section 5 | L Split outdoor unit HM 12Split...
Miniature circuit breaker (protecting the out- CAUTION door unit) When SF1 is set to „ ” - the HM 6Split / HM 12Split Miniature circuit breaker (protecting the STB unit switches the QN10 valve to the central heating and power) and heating takes place according to thermostat BT30.
-tariff control. CAUTION When a 400V connection is used, the maximum pow- er of the electric module used in the HM 6Split / HM 12Split unit is 9kW. CAUTION In the case of a dual tariff power supply, it is advisa- ble to connect the neutral wire from the power supply circuit (meter).
Page 30
When a 230V connection is used, the maximum pow- The L Split unit must be earthed before connecting er of the additional heat used in the HM 6Split / HM the appliance via the cable. Wiring must be secured so 12Split unit is 4.5kW.
Page 31
The temperature sensor BT25 (included) should be an enclosure next to the electrical distribution unit. connected to the HM 6Split / HM 12Split unit via ter- Use unscreened multi-core cable of at least 0.5 mm², minal block AA3-X6: 5 and AA3-X6: 6. For the location from the enclosure to control module.
3kW. CAUTION The temperature on the thermostat must be set ac- cording to the system requirements. If the tempera- ture is too high, it can damage the system. Section 7 | Commissioning and adjusting HM 6Split HM 12Split...
To prevent corrosion damage, three basic parameters of water composition must be controlled: Filling and venting the climate system dissolved oxygen content, and HM 6Split / HM 12Split 2. electrical conductivity and 3. pH. Open the vent valves at the highest point of the Oxygen content and electrical conductivity are re- climate system.
Commissioning Pump speed CAUTION Commissioning of the system must be carried out by The circulation pump in HM 6Split / HM 12Split is fre- a person with appropriate authorizations and manufac- quency-controlled and adjusts itself using control and turer’s authorization! based on heating / hot water demand.
Go to menu 5.2 System settings and turn off the heat pump. CAUTION Select the auto or manual operating mode when the indoor unit is to be used again with the heat pump. HM 6Split Section 7 | Commissioning and adjusting HM 12Split...
You can: • scroll in menus and between options. • increase and decrease the values. • change page in multiple page instructions (for example help text and service info). Section 8 | Control - Introduction HM 6Split HM 12Split...
MENU 5. Required additional equipment PV Split. This symbol indicates whether pool heating is active. Required additional equipment IPP Split. This symbol indicates whether cooling is active. HM 6Split Section 8 | Control - Introduction HM 12Split...
Page 38
To change and return to the The help text often consists of several windows that original value, press the Back button. you can scroll between using the control knob. Section 8 | Control - Introduction HM 6Split HM 12Split...
3.1 - service info 3.2 - compressor info 3.3 - add. heat info 3.4 - alarm log 3.5 - indoor temp. log The accessory EP Split is required if the output AA3: X7 is occupied. Section 9 | Control HM 6Split HM 12Split...
The EP Split additional equipment is necessary. additional equipment is necessary. additional equipment is necessary. additional equipment is necessary. additional equipment is necessary. additional equipment is necessary. additional equipment is necessary. The Modbus Split Section 9 | Control HM 6Split HM 12Split...
Factory setting:-15.0 DOT C 7/18 Control of external sensors In this menu we have the possibility to check the al- lowed values for external sensors. More information after selecting " ? ". HM 6Split Section 9 | Control HM 12Split...
Page 44
+ 55 for radiator heating. 14/18 Heating curve In this menu it is possible to edit the heating curve specified for the HM 6Split / HM 12Split unit. More 9/18 Installed slaves information after selecting " ? ". In this menu, it is possible to select slave devices.
15/18 Op mode In this menu, you can select the operating mode for Menu 1 - Indoor climate the HM 6Split / HM 12Split unit. More information af- ter selecting " ? ". The menu CLIMATE OF ROOMS is used to modulate Factory setting: auto the settings for the heating system.
Page 46
Confirm the new setting by pressing the OK button. Curve 0 is an own curve created in menu 1.9.7 . This menu is intended for advanced users. This menu has several sub-menus. Section 9 | Control HM 6Split HM 12Split...
Page 47
This means that HM 6Split / HM 12Split never calculates a temperature lower than that set here. If there is more than one climate system the setting can be made separately for each system. HM 6Split Section 9 | Control HM 12Split...
Page 48
Menu 1.9.5 - cooling settings (if active) Menu 1.9.8 - point offset You can use HM 6Split / HM 12Split to cool the house Make the correction for the heating curve at a certain during hot periods of the year. More information after outdoor temperature here.
Page 49
- Lux mode gives the greatest possible amount of hot water. In this mode the immersion heater may be partially used to heat hot water, which may in- crease operating costs. HM 6Split Section 9 | Control HM 12Split...
Page 50
No changes can be made. The information is on several pages. Turn the control knob to scroll between the pag- es. More information after selecting " ? ". Section 9 | Control HM 6Split HM 12Split...
Page 51
Menu 4.1.3 - internet To facilitate fault-finding the heat pump operating sta- Here you make settings for connecting HM 6Split / tus at alarm alerts is stored here. You can see infor- HM 12Split to the internet. More information after se- lecting "...
Page 52
You cannot deselect "compressor" in In this menu, we configure advanced functions of the manual mode. HM 6Split / HM 12Split controller. More information after selecting " ? ". Operating mode add. heat only Menu 4.9.1 - op. prioritisation In this operating mode the compressor is not active, only additional heat is used.
Page 53
400 DM diff. between additional steps: 30 DM CAUTION Higher value on "start compressor" gives more com- pressor starts, which increase wear on the compressor. Too low value can give uneven indoor temperatures. HM 6Split Section 9 | Control HM 12Split...
Cooling settings Submenu SERVICE In the factory settings of the HM 6Split / HM 12Split Go to the main menu and hold the Back button in for 7 the cooling is deactivated and requires activation in seconds to access the Service menu.
Page 55
Factory setting: speed 4: 100% Set the speed for the five different selectable speeds for the fan here. CAUTION An incorrectly set ventilation flow can damage the house and may also increase energy consumption. HM 6Split Section 9 | Control HM 12Split...
Page 57
(EB101 = Slave 1, CL11 = Pool 1 etc.). Mark “search installed slaves" and press the OK but- ton to automatically find connected slaves for the Hot water charging master heat pump. HM 6Split Section 9 | Control HM 12Split...
Page 58
5.2.4. A detailed description of programming the accesso- ries can be found in the instructions for the individual accessories. Section 9 | Control HM 6Split HM 12Split...
Page 59
Menu 5.7 - start guide ries can be found in the instructions for the individual accessories. The first time you start the HM 6Split / HM 12Split, Menu 5.3.21 - flow sensor / energy meter the start guide starts automatically. In this menu we have the ability to run it manually.
Page 60
This option locks after 24 hours, restart of display or onds before and after the compressor in the heat pump program updating. speed during operation heating, hot water, pool, cooling Setting range: auto / manual Factory setting: auto Section 9 | Control HM 6Split HM 12Split...
(VDC) Servicing should only be carried out by persons with 351,0 3,256 the necessary expertise. 251,6 3,240 When replacing components in the HM 6Split / HM 12Split, only original spare parts should be used. 182,5 3,218 133,8 3,189 Emergency mode...
Page 62
OK button is held in during start up until the green lamp starts to illuminate (takes about 10 seconds). Section 10 | Service HM 6Split HM 12Split...
Page 63
3. The present values from the controller are saved in a file in the USB memory at the set interval until “activated" is unticked. IMPORTANT Untick "activated" before removing the USB memory. HM 6Split Section 10 | Service HM 12Split...
Page 64
Connect the hose to the XL10 drain valve of the system. 2. Then open the drain valve to empty the heating system. 3. Open the safety valve to remove the created un- derpressure. XL10 Section 10 | Service HM 6Split HM 12Split...
If the room temperature problem that caused the alarm. The status lamp will therefore continue to be red. is only low in cold weather the curve slope in HM 6Split Section 11 | Disturbances in comfort HM 12Split...
Minimum time between compressor starts has not been reached. – Wait 30 minutes and then check if the compres- sor has started. • Alarm tripped. – Follow the display instructions. Section 11 | Disturbances in comfort HM 6Split HM 12Split...
More accessories are available on the web- site //www.alpha-innotec.com Room unit RBE RBE means that control and monitoring of the con- troller can be carried out in a different part of your home to where it is located. HM 6Split Section 12 | Accessories HM 12Split...
N to the terminal block AA2-X4: 10 • connect wire PE to the terminal AA2-X4: 9 All connections should be made in accordance with the figure below. 8 9 10 11 12 13 AA2-X4 HM 6Split/ SHB 10 HM 12Split Externt External Zewnętrzne AA2-X4...
XL13 XL14 Pipe connections Connection, heating medium supply, Ø22 mm for HM 6Split and HM 12Split, Connection, heating medium return, Ø22 mm for HM 6Split and HM 12Split, Connection, HW heating medium supply, Ø22 mm for HM 6Split and HM 12Split, XL10 Connection, GW1/2”...
Rated voltage 230V 1N AC 50Hz / 400V 3N AC 50Hz Energy class (in accordance with ErP . at supply temp. 55°C) applies to package L 6Split + HM 6Split, L 12Split + HM 12Split Outdoor unit Unit L 6Split...
Page 72
Max. operating current and recommended fuse rating HM 6Split HM 12Split HM 12Split Unit + L 6Split for 3x400 V connection + L 8Split + L 12Split Max. operating current, compressor Max. operating current of heat pump including 3 kW...
EC Declaration of Conformity Declaration of Conformity The undersigned confirms that the following designated device(s) as designed and marketed by us fulfill the standardized EC directives, the EC safety standards and the product-specific EC standards. In the event of modification of the device(s) without our approval, this declaration shall become invalid.
Page 84
GmbH Industriestraße 3 D-95359 Kasendorf E info@alpha-innotec.de W www.alpha-innotec.de alpha innotec – an ait-deutschland GmbH brand...
Need help?
Do you have a question about the HM 6Split and is the answer not in the manual?
Questions and answers