1-3. Dry operation

The compressor rotation frequency shall change according to the temperature, set temperature, and
room temperature variation which the room temperature sensor of the indoor unit has detected as
shown in the table below.
Zone is defined by set temperature and room temperature.
• Compressor frequency range
Model name
AGYG09KVCB
AGYG12KVCB
AGYG14KVCB
• Compressor control based on room temperature
1-3. Dry operation
Outdoor temperature zone
Room temperature drops
X zone
Ts+0.5°C
J zone
Ts
-1.5°C
Y zone
X zone
J zone
Y zone
X zone
J zone
Y zone
X zone
J zone
Y zone
Room temperature rises
Ts: Set temperature
- (04-4) -
Unit: rps
Operating frequency
30
20
0
26
18
0
22
18
0
Ts+1.5°C
Ts-0.5°C
1. Compressor frequency control