ADDRESSABLE SELF TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LEDs
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
ILLUMINATION (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used in places where
emergency luminaires are needed. Each
luminaire must be permanently connected to
mains power supply. In normal operation (L1
connected to L) the led strip lights and the battery
is charging. In case of a mains power supply
failure
the luminaire
automatically in emergency mode (powered by
its battery). When the mains power supply is
restored the device turns to normal operation.
Address Operation
The luminaires can be connected to a GR-6500
address panel. For address operations refer to
the installation manual of the panel.
For address module connections see page 3.
For dip-switch addressing selection see page 3, 4
and 5.
INSTALLATION
To install the luminaire follow the installation
instructions on page 3.
Battery Charging
The battery charging is completely controlled.
Thereby, the best possible battery maintenance is
achieved, as well as the elongation of its
duration. When the battery has completely
charged, it charges with a maintenance current.
Page 1 from 5
GR-938/15L/ADR GR-938/30L/ADR GR-939/15L/ADR GR-939/30L/ADR
3.4W / 3.8VA
3.6V/0.6Ah
15 white LEDs
105lm / 105lm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
810gr.
Thank you for your trust in our products.
Olympia Electronics - European manufacturer.
will
light the led strip
(for LED MODULE Specs. see page 5)
220-240V AC/50-60Hz
4.5W / 4.9VA
3.6V/1.5Ah
From overcharge and deep discharge
Charge, Lamp Fault, Battery Fault indication LED
24h
90min
30 white LEDs
210lm / 210lm
IP65
5 to 40 C
Up to 95%
Bayblend FR3010, transparent polycarbonate
363 x 145 x 73 mm
880gr.
3 years (1 year for the battery)
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost its
energy. During this operation the luminaire enters
the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Manual Test
The manual test can be conducted only if the
mains power supply and the battery is connected.
By pressing the TEST/RESET button briefly
(page 3) an operation test is initiated. During this
test period all indication LEDs are OFF.
Tests
Normally
the
autonomy tests are programmed by the control
panel and the test results are sent to the control
panel.
If the luminaire is not connected to GR-6500
panel, the following automatic tests executed:
Automatic Operational Test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
mains power supply and the battery should be
connected.
3.3W / 3.7VA
5.3W /5.6VA
3.6V/3Ah
180min
15 white LEDs
30 white LEDs
105lm / 105lm
210lm / 210lm
o
illumination
source
923939015_09_004
950gr.
and
the

Advertisement

loading

Summary of Contents for olympia electronics GR-938/15L/ADR

  • Page 1 ADDRESSABLE SELF TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LEDs TECHNICAL CHARACTERISTICS (for LED MODULE Specs. see page 5) GR-938/15L/ADR GR-938/30L/ADR GR-939/15L/ADR GR-939/30L/ADR OPERATION VOLTAGE 220-240V AC/50-60Hz MAXIMUM POWER CONSUMPTION 3.4W / 3.8VA 4.5W / 4.9VA 3.3W / 3.7VA 5.3W /5.6VA BATTERIES (Ni-Cd) 3.6V/0.6Ah...
  • Page 2 Automatic Autonomous Test 5. I s not allowed to discard batteries in to The Automatic Autonomous Test is conducted c o m m o n t r a s h b i n s , t h e y m u s t b e and measures the device’s back up operation discarded only in battery recycling...
  • Page 3 INSTALLATION INSTRUCTIONS FOR WALL OR CEILING MOUNTING 1 Remove the diffusor. Place a flat blade screwdrivers and pull up gently the reflector. 2 Install the included plastic cover in to the unused hole and install the base plastic (with the included mounting screws and plugs).
  • Page 4 Address Dipswitch Address Dipswitch Address Dipswitch Address Dipswitch Address Dipswitch Address Dipswitch setting setting setting setting setting setting 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8...
  • Page 5: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-938/30l/adrGr-939/15l/adrGr-939/30l/adr