Download Print this page
olympia electronics GR-938/4P Manual

olympia electronics GR-938/4P Manual

Advertisement

Quick Links

WATERPROOF SELF TESTING ΜΑΙΝΤΑΙΝΕD EMERGENCY LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
ILLUMINATION (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used in places where
emergency luminaires are needed. Each
luminaire must be permanently connected to
mains power supply. In normal operation the
led strip lights and the battery is charging. In
case of a mains power supply failure the
luminaire will light the led strip automatically
in emergency mode. When the mains power
supply is restored the device turns to normal
operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 3.
OPERATION
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost
its energy. During this operation the luminaire
enters the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Battery charging
The battery charging is completely controlled.
In this case, is achieved the perfect battery
maintenance , as well as the elongation of its
duration. When the battery has completely
charged, it charges with a maintenance
current.
Manual Test
The manual test can be conducted only if the
main power supply and the battery is
Page 1 from 4
GR-938/4P
4.6W/5 VA
4.8V/1.5Ah
4 white power LED's
175lm / 350lm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
915gr.
Thank you for your trust in our products.
Olympia Electronics - European manufacturer.
( for LED MODULE Specs. see page 4)
GR-938/6P
220-240V AC/50-60Hz
5.8W/6.2 VA
4.8V/3Ah
From overcharge and deep discharge
Charge, lamp fault, fault indication LED, TEST button
24 h
90 min
6 white power LED's
245lm / 480lm
IP65
5 to 40 C
Up to 95%
ABS/PC, PC
360 x 145 x 73 mm
1005gr.
3 years (1 year for the battery)
connected. By pressing the TEST/RESET
button briefly (page 3) an operation test is
initiated. During this test period all indication
LEDs are OFF.
Automatic test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
main power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the luminaire`s back up
operation. This test is conducted automatically
every six months. In order to be performed, the
main power supply and the battery should be
connected (the battery should be charged). If
the battery is not charged, the test is postponed
until the battery is completely charged. If the
luminaire's duration is lower than the named
during the Automatic Autonomous Test, the
battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated in the technical characteristics. During
emergency mode, a LED strip test is also
performed.
Resetting Errors
Push the TEST/RESET button for 5 seconds, to
extinguish all the indicated LED errors (page 3).
Then the luminaire enters regular operation
GR-939/4P
GR-939/6P
5.2W/5.5 VA
6.1W/6.4 VA
4.8V/4Ah(Ni-MH)
3 h
4 white power LED's
6 white power LED's
175lm / 350lm
245lm / 480lm
o
1060gr.
923939008_09_017

Advertisement

loading

Summary of Contents for olympia electronics GR-938/4P

  • Page 1 TYPICAL WEIGHT 3 years (1 year for the battery) GUARANTEE Thank you for your trust in our products. Olympia Electronics - European manufacturer. GENERAL connected. By pressing the TEST/RESET These luminaires are used in places where button briefly (page 3) an operation test is emergency luminaires are needed.
  • Page 2 mode. 2. The device must be connected to the mains Indication LED status power supply through a fuse depended on the (with connected mains power supply). total amount of the line’s power load. Charge In case of battery or lamp replacement, these On: Good charge current.
  • Page 3 INSTALLATION INSTRUCTIONS 1 Remove the diffusor. Place simultaneously a flat blade screwdriver and pull up gently the reflector. 2 Install the included plastic cover in to the unused hole and install the base plastic (with the included mounting screws and plugs). 3 Always use in any case round mains cable, with external diameter of 6-9mm (H05RN-F type 2x1mm²...
  • Page 4 Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-938/6pGr-939/4pGr-939/6p