Page 2
AR3500 Introduktionssidorna består huvudsakligen av bilder. För översättning av de engelska texter som används, se respektive språksidor. The introduction pages consist mainly of pictures. For translation of the English texts used, see the respective language pages. Introduksjonssidene består hovedsakelig av bilder. For oversettelse av de engelske tekstene, se de respektive språksidene Les pages de présentation contiennent principalement des images.
Page 3
AR3500 Type [mm] [mm] [mm] [mm] AR3510 1057 1016 1067 AR3515 1567 1526 1577 1466 AR3520 2073 2031 2083 1971 Mounting Fig. 1: The mounting brackets on delivery.
Page 4
AR3500 Mounting Fig. 2a: Mounting on threaded bars. Fig. 2b: Mounting on threaded bars inside unit.
AR3500 90° Service hatch Fig. 3: Function of the snap fixing Water connections Fig. 4: The water coil is connected inside the unit through holes which are made (during installation) on the upper side or through the side of the unit, possible places are marked with punch marks. SIRe SIRe Fig.
Page 6
AR3500 Accessories SIRe SIReB SIReAC SIReAA SIReB SIReUR SIReRTX 70x33x23 mm SIReUR 114x70x50 mm SIReWTA SIReWTA SIReCJ4 SIReCJ6 SIReCC603 SIReCC605 SIReAC/SIReAA SIReCC610 10 m SIReCJ4/SIReCJ6 SIReCC615 15 m SIReCC640 40 m SIReCC403 SIReCC405 10 m SIReCC410 SIReCC415 SIReRTX SIReCC VLSP DN15 VKF15LF VKF15NF...
Page 9
AR3500 SIReB Basic AR3500 A / AR3500 E SIReUB1 SIReRTX SIReB1/B2/B1EC 230V~ (optional) ROOM Pot. Unit ID ACTUATOR SUPPLY SIReCC6XX L=2m (max 50 m) SIReCC6XX (max 50 m) SIReB1/B2/B1EC 230V~ ROOM Pot. Unit ID ACTUATOR SUPPLY SIReCC6XX (max 50 m) SIReB1/B2/B1EC 230V~ ROOM...
Page 10
AR3500 SIReB Basic AR3500 W SIReUB1 SD230 SIReRTX SIReB1/B2/B1EC 230V~ (optional) ROOM Pot. Unit ID ACTUATOR SUPPLY SIReCC6XX L=2m (max 50 m) L=1,5m SIReCC6XX (max 50 m) SD230 SIReB1/B2/B1EC 230V~ ROOM Pot. Unit ID ACTUATOR SUPPLY SIReCC6XX (max 50 m) SD230 SIReB1/B2/B1EC 230V~...
Page 11
Output * Outlet Water Pressure position temp. flow drop air temp. flow drop [kW] [°C] [l/s] [kPa] [kW] [°C] [l/s] [kPa] AR3510W 2300 13,4 0,10 16,4 38,8 14,7 1100 0,03 10,1 45,6 0,12 AR3515W 3400 19,8 0,14 25,1 39,6 0,31...
Page 12
AR3500 Output charts water AR3500 AR3500WLL Special coil Supply water temperature:55 °C Water temperature: 55/35 °C Room temperature: +18 °C Room temperature: +18 °C Outlet air temperature: +35 °C* Type Airflow Output Return water Water Pressure Output * Outlet Water Pressure position temp.
For the protection of wider doorways, Frico mounting and operating instructions. several units can be mounted next to each other. Application area Minimum distance from outlet to floor for The AR3500 air curtain unit is supplied electrically heated units is 1800 mm.
Page 15
3. After service, repairs and maintenance Note that the unit shall be preceded by a close the service hatch and make sure that regulating valve, see Frico valve kit. the snap fixings lock properly. To access the connections (DN20, 3/4”,...
AR3500 Maintenance Fan replacement Since fan motors and other components are 1. Determine which of the fans is not maintenance free, no maintenance other than functioning. cleaning is necessary. The level of cleaning 2. Disconnect the cables to the relevant fan. can vary depending on local conditions.
Page 17
AR3500 • That there is enough water flow. • That incoming water is heated enough. If the fault cannot be rectified, please contact a qualified service technician. Residual current circuit breaker (E) When the installation is protected by means of a residual current circuit breaker, which trips when the appliance is connected, this may be due to moisture in the heating element.
Page 18
Main offi ce Frico AB Tel: +46 31 336 86 00 Box 102 SE-433 22 Partille mailbox@frico.se Sweden www.frico.se For latest updated information and information about your local contact: www.frico.se...