The cross-section of the cable and the line protection devices must correspond to those indicated in
the wiring diagram.
The connections to the electrical control panel must be made maintaining the stated IP protection
rating.
If you use a residual current device to protect the power line, in units with inverter, use type "B" or "B+"
residual current devices, with minimum tripping threshold of 300 mA and delayed tripping.
The electrical connections to potential-free contacts, which are powered by external sources, must be
suitably protected against overcurrent and earth faults.
The circuit of the potential-free contacts inside the electrical control panel is made using orange cable.
We reserve the right to make changes without any prior notice.
UATYQ*Y1
Packaged Rooftop
4P522680-1
Translation from original instructions
Installation manual
27