A pallet is secured under the unit so that it can also be unloaded and handled with a suitable forklift truck.
If anti-vibration mounts are installed under the base of the unit, this must be done with the unit raised by no more than
200 mm from the ground and without putting any parts of the body under it.
Before sliding out the pallet, remove the screws fixing it to the unit.
Use a 10 mm spanner to unscrew the screws that are visible through the slotted holes of the base.
After the pallet has been removed, the unit should be lifted using only and solely the lifting slings and tubes supplied
with it, inserted in the lifting eyes marked with the plates provided (yellow plates).
For smaller sizes "UATYQ20A***Y1, UATYQ25A***Y1 and UATYQ30A***Y1", the slings can be inserted directly
through the lifting eyes.
For smaller sizes "1.2, 3.2 and 4.2", the slings can be inserted directly through the lifting eyes.
To prevent the slings from being damaged on the edges of the lifting eyes, use suitable protective
devices.
To prevent the slings from touching the unit, suitable protective devices must be placed on the upper
edges.
Translation from original instructions
Installation manual
14
Fig. 1 Detail of position of pallet fixing screws
Fig. 2 Lifting with slings