Veris Industries E50 Series Installation Manual page 24

Power monitoring
Table of Contents

Advertisement

Installation Guide
Power Monitoring
E50B1, E50C2, E50C3
Modbus Point Map (cont.)
R/W NV Format
• 169
R/W NV
• 170
R/W NV
• 171
R/W NV
• 172
R/W NV
• 173
R/W NV
• 174
R/W NV
• 175
R/W NV
• 176
R/W NV
• 177
R/W NV
• 178
R/W NV
• 257/258 R
NV
• 259/260 R
NV
• 261/262 R
• 263/264 R
• 265/266 R
• 267/268 R
• 269/270 R
• 271/272 R
• 273/274 R
• 275/276 R
• 277/278 R
• 279/280 R
• 281/282 R
• 283/284 R
• 285/286 R
• 287/288 R
• 289/290 R
• 291/292 R
• 293/294 R
• 295/296 R
• 297/298 R
• 299/300 R
• 301/302 R
• 303/304 R
• 305/306 R
• 307/308 R
• 309/310 R
NV
ZL0103-0C
Page 24 of 26
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Find Quality Products Online at:
Units
Scale
Range
UInt
UInt
UInt
UInt
1-42, 146,
155-157,
UInt
257-336
UInt
UInt
UInt
UInt
UInt
Float
kWh
Float
kWh
Float
kW
Float
kVAR
Float
kVA
Float
Ratio
0.0-1.0
Float
Volt
Float
Volt
Float
Amp
Float
kW
Float
kW
Float
kW
Float
Ratio
0.0-1.0
Float
Ratio
0.0-1.0
Float
Ratio
0.0-1.0
Float
Volt
Float
Volt
Float
Volt
Float
Volt
Float
Volt
Float
Volt
Float
Amp
Float
Amp
Float
Amp
Float
Float
Hz
45.0-65.0
Float
kVAh
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
GlobalTestSupply
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
www.
Log Register Pointer 1 –
Default is 1 (Real Energy MSR)
Log Register Pointer 2 –
Default is 2 (Real Energy LSR)
Log Register Pointer 3 –
Default is 29 (Reactive Energy
MSR)
Log Register Pointer 4 –
Default is 30 (Reactive Energy
LSR)
Log Register Selection – Write the number of the 16 bit register to be logged.
Log Register Pointer 5 –
To log a 32 bit value (such as accumulators and floating point values) two log
Default is 37 (Real Demand)
registers must be used, one each for the most and least significant register
Log Register Pointer 6 –
(MSR & LSR).
Default is 38 (Reactive Demand)
Log Register Pointer 7 –
Default is 39 (Apparent Demand)
Log Register Pointer 8 –
Default is 155 (Month/Day)
Log Register Pointer 9 –
Default is 156 (Year/Hour)
Log Register Pointer 10 –
Default is 157 (Minutes/Seconds)
Floating Point Data
Real Energy Consumption (clear via reset register)
Real Energy Consumption (clear via reset register)
Total Instantaneous Real Power
Total Instantaneous Reactive Power
Total Instantaneous Apparent Power
Total Power Factor (Total KW / Total KVA)
Voltage, L-L, Average of 3 Phases
Voltage, L-N, Average of 3 Phases
Current, Average of 3 Phases
Real Power, Phase A
Real Power, Phase B
Real Power, Phase C
Power Factor, Phase A
Power Factor, Phase B
Power Factor, Phase C
Voltage, Phase A-B
Voltage, Phase B-C
Voltage, Phase A-C
Voltage, Phase A-N
Voltage, Phase B-N
Voltage, Phase C-N
Current, Instantaneous, Phase A
Current, Instantaneous, Phase B
Current, Instantaneous, Phase C
Reserved, returns 0x7FC00000 (QNAN)
Frequency (derived from Phase A)
Apparent Energy Consumption
.com
Description
sales@GlobalTestSupply.com
TM
09141

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E51 seriesE50b1E50c2E50c3