Power Monitoring
E50B1, E50C2, E50C3
UI for Setup
Back
From:
SETUP > PASWD
Back
Current
Transformer
Back
Back
Potential
Transformer
Back
Back
To Setup p. 2 "SPLOS"
† When leaving this parameter screen using the right button ( ), the display will
briefly indicate "SAvEd)" to confirm that any changes made have been accepted.
ZL0103-0C
Page 14 of 26
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Find Quality Products Online at:
To Setup p. 2 "SPASS"
RS-485
Output
ADDR
S COM
--------
001
CT V
--------
S CT
1.0
.33
SYSTM
--------
3L-1n
S SYS
3L
2L-1n
System
2L
Type
1L-1n
RATIO
S PT
--------
001.00
Next
V LL
--------
S
V
00600
Sytem
Voltage
Next
MX KW
--------
S PWR
103.92
Sytem
Next
Voltage
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
GlobalTestSupply
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
www.
BAUD
--------
38400
19200
9600
4800
2400
1200
Next
CT SZ
Set Current Transducer:
--------
CT V - CT Input Voltage: + or – to Select 1.0 or .33V.
100
CT SZ - CT Size: in Amps. Maximum is 32000 Amps.
Next
Set System Configuration:
SYSTM: + or – to step through the following System Type options:
System
Reg 130 CTs Description
3L-1n
40
3L
31
2L-1n
12
2L
11
1L-1n
10
Next
Set Potential Transfomer Ratio:
RATIO – Potential transformer step down is RATIO:1. Default is 1:1
(No PT installed). See Install for wiring diagrams. This value must be
set before the System Voltage (if used).
Set System Voltage:
V LL – The nominal Line to Line Voltage for the system. This is used
by the meter to calculate the theoretical maximum system power, and
as the reference voltage for setting the Phase Loss threshold.
Maximum is 32000 Volts. For system type 1+N (10), this is a Line to
Neutral Voltage, indicated by "V LN". Note: the meter will reject settings
that are not within the meter's operating range when divided by the PT
ratio.
System Power:
MX KW – The theoretical Maximum System Power is calculated by the
meter from the System Voltage, CT size, and System Type. Power
Factor is assumed to be unity. The value of System Power is used to
determine which combinations of pulse weight and duration are valid
and will keep up with the maximum power the meter will see. This value
is read only.
Set Communications Parameters:
PAR
ADDR - Modbus Address: 1 – 247.
--------
+ increments the selected (blinking) digit.
nOnE
- selects the digit to the left.
EvEn
BAUD - Baud Rate: 1200 – 38400 Baud
Odd
PAR - Parity: Odd, Even, None
+
or
to step through the options.
3
Wye Three Phase: A, B, & C with Neutral (Default).
3
Delta Three Phase: A, B & C; no Neutral
2
Single Split Phase: A & B with Neutral
1
Single Phase: A & B; no Neutral
1
Single Phase: A to Neutral
Note: Bold is the Default.