Installing A Fan Module; Replacing A Power Supply Module; Replacing An Ac Power Supply - Cisco Nexus 9300-FX Hardware Installation Manual

Table of Contents

Advertisement

Installing a Fan Module

Do not touch the electrical connectors on the back side of the module and prevent anything else from coming
Caution
into contact with and damaging the connectors.
Installing a Fan Module
Before you begin
• A fan slot must be open and ready for the new fan module to be installed.
• You must have a new fan module on hand and ready to install within one minute of removing the original
• The new fan module must have the same airflow direction as the other fan and power supply modules
Step 1
Holding the fan module by its handle, align the back of the fan module (the side with the electrical connectors) to the
open fan slot in the chassis.
Step 2
Slide the fan module into the slot until it clicks in place.
Step 3
Verify that the Status (STS) LED turns on and becomes green.

Replacing a Power Supply Module

The switch requires two power supplies for redundancy. With one power supply providing the necessary
power for operations, you can replace the other power supply during operations so long as the new power
supply has the same airflow direction as the other modules in the chassis.
You can replace a power supply with another supported power supply that has the same power source type
(AC) and the same wattage rating as the other installed power supply. Additionally, the airflow direction of
the power supply must match the airflow direction of the installed fan modules. For the airflow direction used
by the switch, see the coloring of the fan modules. The following list describes the power supplies supported
by this switch.
• N9K-PAC-350W-PE (350-W, port-side exhaust (blue latch) power supply)
• N9K-PAC-350W-PI (350-W, port-side intake (burgundy latch) power supply)
• NXA-PDC-440W-PE (440-W, port-side exhaust (blue latch) power supply)
• NXA-PDC-440W-PI (440-W, port-side intake (burgundy latch) power supply)

Replacing an AC Power Supply

You can replace an AC power supply during operations so long as the other power supply provides to the
switch.
Cisco Nexus 9348GC-FXP ACI Mode Hardware Installation Guide
36
fan module if the switch is operating.
installed in the switch. All of these modules must have either burgundy coloring (port-side intake airflow)
or they must all have blue coloring (port-side exhaust airflow).
Replacing Components