Replacing Components; Replacing A Fan Module; Removing A Fan Module - Cisco Nexus 9300-FX Hardware Installation Manual

Table of Contents

Advertisement

Replacing Components

Replacing a Fan Module

You can replace one of the three fan modules at a time while the switch is operating so long as you perform
the replacement within one minute. If you cannot perform the replacement within one minute, leave the original
fan module in the chassis to maintain the designed airflow until you have the replacement fan module on hand
and can perform the replacement.
Caution
If you are replacing a module during operations, be sure that the replacement fan module has the correct
direction of airflow, which means that it has the same airflow direction as the other modules in the chassis.
Also, be sure that the airflow direction takes in air from a cold aisle and exhausts to a hot aisle. Otherwise,
the switch can overheat and shutdown.
If you are changing the airflow direction of all the modules in the chassis, you must shutdown the switch
before replacing all the fan and power supply modules with modules using the other airflow direction. During
operations, all of the modules must have the same direction of airflow.

Removing a Fan Module

Warning
Statement 263—Fan Warning
The fans might still be turning when you remove the fan assembly from the chassis. Keep fingers, screwdrivers,
and other objects away from the openings in the fan assembly's housing.
Step 1
On the fan module that you are removing, press the two sides of the fan module handle next to where it connects to the
fan module and pull on the handles enough to unseat it from its connectors.
Step 2
Holding the handle, pull the module out of the chassis.
Replacing a Fan Module, on page 35
Replacing a Power Supply Module, on page 36