Selecting A Communication Mode - Huawei SUN2000-29.9KTL Quick Manual

Hide thumbs Also See for SUN2000-29.9KTL:
Table of Contents

Advertisement

Installing a DC input power cable (using metal stamping forming contacts)
Positive metal contact
Negative metal contact
Recommended: PV cable
(PV1-F) with a cross-
sectional area of 4 mm
4.5

Selecting a Communication Mode

1. You can choose either the MBUS (PLC) or RS485 communication mode for the SUN2000-
29.9KTL/33KTL-A/36KTL/42KTL.
2. FE communication is optional for the SUN2000-36KTL. If you need to use the FE communication
mode, contact local technical support.
3. If the SUN2000-36KTL adopts FE communication mode, it supports only RS485 and FE
communication modes, and does not support MBUS (PLC) communication mode.
4.6
Installing RS485 Communications Cables
1. When routing communications cables, separate communications cables from power cables to
prevent communication from being affected.
2. An RS485 cable can connect to either a terminal block or an RJ45 network port. It is
recommended that the RS485 cable connect to a terminal block.
Connecting to a terminal block (recommended)
The DJYP2VP2-22 2x2x1 computer cable or a communications cable with a cross-sectional area
2
of 1 mm
and outer diameter of 14–18 mm is recommended.
H4TC0003 (Amphenol)
Ensure that the cable
cannot be removed after
crimped.
2
.
Ensure that cables
are connected
correctly and that
the voltage does not
exceed 1100 V DC.
11
Positive connector
Negative
connector
Click
Ensure
that the
locking nut
is secured.
H4TW0001
(Amphenol)