Adapter for installing process photometers in varivent process connections (20 pages)
Summary of Contents for Endress+Hauser WirelessHART Adapter SWA70
Page 1
Operating Instructions WirelessHART Adapter SWA70 Smart wireless module with power supply for field devices BA00061S/04/en/15.12 Version 2.00.xx 71188915...
WirelessHART Adapter SWA70 Registered trademarks ® ® HART , WirelessHART Registered trademarks of the HART Communication Foundation, Austin, USA ® ® ® ® ® Microsoft , Windows , Windows XP , Windows Vista , Windows 7 and the Microsoft logo are registered trademarks of the Microsoft Corporation.
Safety instructions Designated use The WirelessHART Adapter SWA70 is a smart wireless module designed for the wireless transmission of 4 to 20 mA HART signals from connected field devices to a WirelessHART Fieldgate. Information about the designated use of the connected field devices and the Fieldgate is provided in the devices' individual operating manuals.
The WirelessHART Adapter may not be repaired. If the device is faulty or malfunctions, return the device to Endress+Hauser. Follow the instructions outlined in the "Return" section on Page 98. In the case of devices with a battery unit, the battery unit must be removed before the device is returned.
Technical improvement Endress+Hauser reserves the right to make technical improvements to the hardware and software anytime without prior notice. Such improvements are not documented if they do not affect the operation of the device.
1 Safety instructions WirelessHART Adapter SWA70 Conventions used in this manual Typographical emphasis and special symbols have been used to provide a clear structure to the contents of these Operating Instructions and to highlight important information. Pay particular attention to the safety conventions and icons used in these Operating Instructions.
Page 11
WirelessHART Adapter SWA70 1 Safety instructions Electrical symbols Symbol Meaning Direct current A terminal to which DC voltage is applied or through which direct current flows. Alternating current A terminal to which alternating voltage (sine-wave) is applied or through which alternating cur- rent flows.
CD-ROM. • If you discover that the WirelessHART Adapter is damaged, the device may not be put into operation. In this case, contact your Endress+Hauser sales partner. Where possible, return the device to Endress+Hauser in its original packaging. Endress+Hauser...
WirelessHART Adapter SWA70 2 Identification 2.1.3 Storage and transportation While the WirelessHART Adapter is a robust device, appropriate precautions must be taken to ensure proper storage and transportation: Storage Condition WirelessHART Adapter WirelessHART Adapter Separate battery unit without power supply unit...
2 Identification WirelessHART Adapter SWA70 Ordering information Please refer to the following table for a breakdown of the order number: SWA70 WirelessHART Adapter SWA70 Approval Non-hazardous area ATEX II 2G Ex ia IIC T4 ATEX II 2G Ex ia IIC T4 Gb, ATEX II 2D Ex tb [ia] IIIC IP6x T70°C Db CSA General Purpose CSA C/US IS Cl.I,II,III Div.1 Gp.A-G, NI Cl.I Div.2 AEx ia...
WirelessHART Adapter SWA70 2 Identification Additional radio approvals An adhesive label on the antenna lists the additional radio approvals. 202WW09117711 CMMIT ID 2011DJ5309 Fig. 2-2: Location of the adhesive label that lists the additional radio approvals System requirements The DTM and DD versions of the device descriptions are provided for the WirelessHART Adapter on the CD-ROM supplied.
3 Function and system design WirelessHART Adapter SWA70 Function and system design The WirelessHART Adapter is a smart wireless module that connects HART and 4 to 20 mA field devices to a WirelessHART network. The WirelessHART Adapter sends the measurement and diagnostics information acquired from the field device to the WirelessHART Fieldgate in the form of radio signals.
Page 17
WirelessHART Adapter SWA70 3 Function and system design The WirelessHART Adapter can be powered in one of four ways: with a wide range power unit, an intrinsically safe power unit, a solar module connection or a battery unit. The field device can be powered either via the power supply of the WirelessHART Adapter or via a separate DC voltage power unit or remote I/O.
4 Installation WirelessHART Adapter SWA70 Installation Overview The WirelessHART Adapter can be installed mechanically in three different ways: • Directly on the field device • At a distance from the field device, but connected by a cable (remote mounting) • As a repeater, i.e. without a field device Various replaceable connection adapters can be screwed onto the cable entry of the WirelessHART Adapter depending on the use and the field device connection.
WirelessHART Adapter SWA70 4 Installation Wall Wall <6 cm Pipe <6 cm Fig. 4-1: General installation instructions Design For housing dimensions see the "Mechanical construction" section on Page 109. Fig. 4-2: Side view of the housing Antenna Secondary cable entry for remote mounting or for...
4 Installation WirelessHART Adapter SWA70 Mounting on the field device You require the following tools to mount the WirelessHART Adapter on the field device: • Wrench 24 mm across flats (SW 24) • Wrench 42 mm across flats (SW 42)
WirelessHART Adapter SWA70 4 Installation 6. Align the adapter if necessary. 7. While holding the cable entry with the 24 mm wrench, tighten the fixing nut using the 42 mm wrench (torque 7 Nm). Remote mounting Remote mounting - where the field device and adapter are mounted at a distance from one another - can be required in various situations, such as when: •...
4 Installation WirelessHART Adapter SWA70 4.5.1 Wall mounting You require the following tools to mount the WirelessHART Adapter on the wall: • Wrench 24 mm across flats (SW 24) • Wrench 42 mm across flats (SW 42) • Wrench 8 mm across flats (SW 8) •...
WirelessHART Adapter SWA70 4 Installation 6. Hold the cable entry in position with a wrench and tighten the fixing nut. 7. Preferably use the secondary cable outlet to connect to the field device. 4.5.2 Pipe mounting You require the following tools to mount the WirelessHART Adapter on a pipe: •...
4 Installation WirelessHART Adapter SWA70 2. Screw the angle bracket onto the fixing bracket with the four Allen screws supplied (torque 4 Nm). 3. Fasten the WirelessHART Adapter on the angle bracket. See the "Wall mounting" section on Page 22. Post-installation check After mounting the WirelessHART Adapter, perform the following final checks: •...
WirelessHART Adapter SWA70 5 Electrical installation Electrical installation The following power supply units are available to supply power to the WirelessHART Adapter: • Wide range power unit • Solar module connection • Power unit, intrinsically safe • Battery unit The field device can be powered either via the power supply of the WirelessHART Adapter or via a separate power supply.
Page 26
5 Electrical installation WirelessHART Adapter SWA70 Field device – supply output Common types of connection: Power 2-wire device, adapter powered Charge HART modem/Handheld Please see manual for more types Ready LED on power Main board supply Fig. 5-1: Block circuit diagram of power supply via wide range power unit...
WirelessHART Adapter SWA70 5 Electrical installation 5.1.2 Power supply via solar module connection The WirelessHART Adapter with the solar module connection is connected to the power supply via the M12 connector. An M12 socket is included in the delivery. For information about mounting and wiring the M12 socket, see the "Connecting the M12 socket"...
5 Electrical installation WirelessHART Adapter SWA70 5.1.3 Power supply via intrinsically safe power unit The WirelessHART Adapter with the intrinsically safe power unit is connected to the power supply via the M12 connector. An M12 socket is included in the delivery. For information about mounting and wiring the M12 socket, see the "Connecting the M12 socket"...
WirelessHART Adapter SWA70 5 Electrical installation 5.1.4 Power supply via battery unit The WirelessHART Adapter with the battery unit is powered by the internal battery. For the technical data, see the "Technical data" section on Page 103. Common types of connection:...
5 Electrical installation WirelessHART Adapter SWA70 1. Disassemble the M12 socket. – Unscrew the pressure screw from the coupling sleeve. – Unscrew the socket insert from the coupling sleeve. For this purpose turn the knurled head screw while holding the coupling sleeve steady.
WirelessHART Adapter SWA70 5 Electrical installation 5.2.2 Wiring for power supply via electronically controlled power supply unit You can mount the WirelessHART Adapter either directly on the field device or at a distance from the field device on a wall or post using a bracket. See the "Wall mounting" section on Page 22 and see the "Pipe mounting"...
5 Electrical installation WirelessHART Adapter SWA70 5.2.3 Wiring for power supply via battery unit You can mount the WirelessHART Adapter either directly on the field device or at a distance from the field device on a wall or post using a bracket. See the "Wall mounting" section on Page 22 and see the "Pipe mounting"...
WirelessHART Adapter SWA70 5 Electrical installation 3. Turn the coupling nut slightly in the counterclockwise direction to release the tension on the cable gland. 4. Open the housing of the WirelessHART Adapter. 5. Guide the cable through the cable gland and into the housing.
5 Electrical installation WirelessHART Adapter SWA70 Wiring diagrams for wide range power unit For the WirelessHART Adapter with a wide range power unit, the following options are available to electrically connect a field device: Connection options Installation in a closed-control loop •...
WirelessHART Adapter SWA70 5 Electrical installation 5.3.2 Field device in a closed-control loop with a communication resistor The following functions are possible with this connection version: • Digital HART communication The WirelessHART Adapter can be connected to an existing installation comprising a HART field device and a power supply system that includes a communication resistor.
5 Electrical installation WirelessHART Adapter SWA70 5.3.3 Two-wire field device with power supplied by internal power supply system The following functions are possible with this connection version: • Power supply to the field device • Current measurement in the 4 to 20 mA range •...
WirelessHART Adapter SWA70 5 Electrical installation 5.3.5 Field devices in multidrop The following functions are possible with this connection version: • Digital HART communication with multidrop mode If you want to operate field devices in the HART multidrop mode, connect the field devices as illustrated below.
5 Electrical installation WirelessHART Adapter SWA70 Wiring diagrams for solar module connection For the WirelessHART Adapter with a solar module connection, the following options are available to electrically connect a field device: Connection options Installation in a closed-control loop • Without a communication resistor, see Page 38.
WirelessHART Adapter SWA70 5 Electrical installation 5.4.2 Field device in a closed-control loop with a communication resistor The WirelessHART Adapter can be connected to an existing installation comprising a HART field device and a power supply system that includes a communication resistor.
5 Electrical installation WirelessHART Adapter SWA70 5.4.3 Two-wire field device with power supplied by adapter The following functions are possible with this connection version: • Power supply to the field device • Current measurement in the 4 to 20 mA range •...
WirelessHART Adapter SWA70 5 Electrical installation Wiring diagrams for intrinsically safe power unit For the WirelessHART Adapter with an intrinsically safe power unit, the following options are available to electrically connect a field device: Connection options Installation in a closed-control loop •...
5 Electrical installation WirelessHART Adapter SWA70 5.5.2 Field device in a closed-control loop with a communication resistor The WirelessHART Adapter can be connected to an existing installation comprising a HART field device and a power supply system that includes a communication resistor.
WirelessHART Adapter SWA70 5 Electrical installation 5.5.3 Four-wire field device The following functions are possible with this connection version: • Current measurement in the 4 to 20 mA range • Digital HART communication if this is supported by the field device.
5 Electrical installation WirelessHART Adapter SWA70 Wiring diagrams for battery unit For the WirelessHART Adapter with a battery unit, the following options are available to electrically connect a field device: Connection options Installation in a closed-control loop • Without a communication resistor, see Page 44.
Page 45
WirelessHART Adapter SWA70 5 Electrical installation If installing with just one signal cable (e.g. common ground for return cable), connect the WirelessHART Adapter as illustrated below: – – Fig. 5-22: WirelessHART Adapter with battery unit – connection of a field device in a closed-control loop without a communication resistor, with one signal cable...
5 Electrical installation WirelessHART Adapter SWA70 5.6.2 Field device in a closed-control loop with a communication resistor The WirelessHART Adapter can be connected to an existing installation comprising a HART field device and a power supply system that includes a communication resistor.
WirelessHART Adapter SWA70 5 Electrical installation 5.6.3 Two-wire field device with power supplied by the adapter The following functions are possible with this connection version: • Power supply to the field device • Current measurement in the 4 to 20 mA range •...
5 Electrical installation WirelessHART Adapter SWA70 5.6.4 Four-wire field device The following functions are possible with this connection version: • Current measurement in the 4 to 20 mA range • Digital HART communication if this is supported by the field device.
WirelessHART Adapter SWA70 6 Operation Operation Display and operating elements – main PCB Warning! • The housing of the WirelessHART Adapter may not be opened in hazardous areas if dust is present. The housing may only be opened in a dusty atmosphere if adequate ventilation ensures the environment is free of dust.
6 Operation WirelessHART Adapter SWA70 6.1.1 Push button Pressing the push button executes a range of functions depending on how long the button is actually pressed. A power supply unit must be connected. When operating with Time pressed Function ≤ 0.2 s...
WirelessHART Adapter SWA70 6 Operation Green light emitting diode: Green LED Battery status Meaning battery status Normal The battery unit will last for at least one more month Flashes at 1 Hz Warning The battery unit will last for less than one month...
6 Operation WirelessHART Adapter SWA70 6.2.2 Light emitting diodes The light emitting diodes indicate the level of power that is available for the field device, for instance. The level of the power supply changes after the power supply has been switched on or returns.
WirelessHART Adapter SWA70 7 Commissioning Commissioning Connected HART field devices We recommend you commission the connected HART field device before commissioning the WirelessHART Adapter. In addition to configuring the field device, the following parameters must also be configured: • HART address = 1 The field device is set to the multidrop mode and the current signal is frozen at 4 mA for the "two-...
7 Commissioning WirelessHART Adapter SWA70 Inserting and connecting the battery unit You must first open the housing to insert the battery unit. Please pay attention to the operational safety instructions. See the "Operational safety" section on Page 7. The battery unit only needs to be inserted for the "WirelessHART Adapter with battery unit" device version.
WirelessHART Adapter SWA70 7 Commissioning Checks during commissioning When commissioning the WirelessHART Adapter, perform the following checks: • Has the battery unit or the electronically controlled power supply unit been inserted correctly? • Is the connecting cable plugged in correctly? •...
7 Commissioning WirelessHART Adapter SWA70 3. Click Ok in the dialog box that appears to start the Found New Hardware Wizard. – Select the Not this time option and press Next. 4. Insert the CD supplied into the CD drive and press Next.
WirelessHART Adapter SWA70 7 Commissioning 5. The Customer Information dialog box is displayed. – Enter your user name and your organization. – Click Next. – The Select Setup dialog box is displayed. – Select Full. – If an older version of the adapter DTM is already installed, click the Automatic Upgrade button.
Page 58
7 Commissioning WirelessHART Adapter SWA70 2. If you are using the accompanying FieldCare Device Setup, switch the license from Easy to Advanced. For this purpose, open the Help menu and click Licensing Information. – Open the DTM Catalog menu and click Update. The Update DTM Catalog dialog box is displayed.
WirelessHART Adapter SWA70 8 Configuration Configuration Creating a FieldCare project Creating a FieldCare project allows you to configure the WirelessHART Adapter via the DTM. For this purpose the WirelessHART Adapter must be connected to the power supply unit and be in the communication mode.
Page 60
8 Configuration WirelessHART Adapter SWA70 2. Right-click HART Communication DTM and select Configuration in the context menu. – The user interface of the HART communication DTM opens in the right-hand pane. – Change the following parameters by selecting the values listed below from the individual lists.
Page 61
WirelessHART Adapter SWA70 8 Configuration 3. Right-click HART Communication and select Connect in the context menu. – The connection is established. 4. Right-click HART Communication and select Create Network in the context menu. – The HART communication DTM scans the network and adds all the HART devices it finds to the network.
8 Configuration WirelessHART Adapter SWA70 Opening the DTM of the WirelessHART Adapter 1. If the WirelessHART Adapter is not yet connected, in the network view right-click "WirelessHART Adapter" and select Connect in the context menu. – The WirelessHART Adapter is connected and one arrow turns green.
WirelessHART Adapter SWA70 8 Configuration Online parameterization 8.3.1 Identification The parameters that are required to identify the WirelessHART Adapter can be configured in the adapter DTM. The default settings appear in the individual input boxes. 1. Click Identification in the DTM navigation tree.
Page 64
8 Configuration WirelessHART Adapter SWA70 Parameter Meaning Example Default Country Code Code for the country in which the WirelessHART Adapter is United States Germany operated. – Controls the signal strength; if the WirelessHART Adapter is not already connected to a network, the signal strength is set to 0 dBm in accordance with national restrictions.
WirelessHART Adapter SWA70 8 Configuration 8.3.2 Wireless communication The parameters that are required to integrate the WirelessHART Adapter into a wireless network can be configured in the adapter DTM. 1. Click Wireless Communication in the DTM navigation tree. – You can enter text in the white fields. Press Enter to save your changes.
Page 66
8 Configuration WirelessHART Adapter SWA70 Parameter Meaning Example Default Join Key Network password, 8 character hexadecimal, Part 3 of 4 33333333 2B204861 Part 3 of 4 Join Key Network password, 8 character hexadecimal, Part 4 of 4 33333333 75736572 Part 4 of 4 Join Shed Time Time in hh.mm.ss that the adapter is given to attempt to join the...
WirelessHART Adapter SWA70 8 Configuration 8.3.3 Wired communication The parameters that are required to set up wired HART communication between the WirelessHART Adapter and one or more HART field devices can be configured in the adapter DTM. 1. Click Wired Communication in the DTM navigation tree.
8 Configuration WirelessHART Adapter SWA70 Parameter Meaning Example Default Scan Subdevices Pressing this button starts the search for connected field devices. – The field devices found are displayed in the WirelessHART Adapter DTM. – If the terminal assignment of the WirelessHART Adapter changes during operation, scanning must be performed again.
WirelessHART Adapter SWA70 8 Configuration 2. The primary variable is permanently linked to the scaled loop current. The scaling and unit can be changed in the DTM navigation tree in the Application Settings/4-20 mA menu. The following variables can be selected as the secondary, tertiary and quaternary variable: –...
Page 70
8 Configuration WirelessHART Adapter SWA70 4-20 mA parameters Parameter Meaning Example Default Primary Variable Unit The unit of the primary variable °C Linearization Mode Determines how the value of the input current is converted Special Linear • Linear: proportional scaling over the set range Curve •...
Page 71
WirelessHART Adapter SWA70 8 Configuration Linearization If the Special Curve option is selected in the Linearization Mode parameter, you must make additional settings in the Linearization window. Comply with the following rules: • You can enter between 2 and 32 value pairs.
8 Configuration WirelessHART Adapter SWA70 8.3.6 Burst mode (application setting) With the burst mode, slave devices can periodically send information, such as process values, without being prompted to do so by the master. The WirelessHART Adapter is responsible for requesting this information from a field device that is connected to the WirelessHART Adapter and forwarding this information to the Fieldgate.
Page 73
WirelessHART Adapter SWA70 8 Configuration We recommend configuring a second burst set for the adapter so that the information of the WirelessHART Adapter is also available for host applications in the Fieldgate. The Primary Variable, Secondary Variable, Tertiary Variable and Quaternary Variable device variables are configured in the "Device Variable Mapping"...
Page 74
8 Configuration WirelessHART Adapter SWA70 Burst mode parameters Parameter Meaning Example Default Burst mode Specifies whether the burst mode is active. Wireless • Off: the burst mode is not active, the input boxes are grayed out and write-protected. • Wireless: the burst mode is active, data can be entered in the input boxes.
Page 75
WirelessHART Adapter SWA70 8 Configuration Parameter Meaning Example Default Burst Command Burst Command Number; more detailed information is provided Number in the HART Specification. • 1: transmits the value of the "Primary Variable" and the unit • 2: transmits the value of the 4 to 20 mA signal and the corresponding value as a percentage •...
Page 76
8 Configuration WirelessHART Adapter SWA70 The graphic below illustrates how burst messages are sent for the "Window" trigger mode. A burst message is sent after the set "Period" if the process value deviates from the last communicated value by more than the defined "Trigger window". In the case of smaller deviations, the process value is sent at the set "Max.
WirelessHART Adapter SWA70 8 Configuration 8.3.7 Event notification (application setting) Event notification is a special application similar to the burst mode. An event notification is sent if there are changes in the device configuration or device status, regardless of whether data are already being sent by burst mode commands.
Page 78
8 Configuration WirelessHART Adapter SWA70 Parameter Meaning Example Default "Event" tab Maximum Update Time Maximum time in hh:mm:ss that is used if no event change 01:00:00 00:30:00 occurs – If no event occurs, the WirelessHART Adapter sends event notification after this length of time.
Page 79
WirelessHART Adapter SWA70 8 Configuration 4. In the Standard Event Mask tab, click the standard events that you want to monitor. 5. Select the Device-Specific Event Mask tab to monitor the device-specific events of the connected field device or the WirelessHART Adapter.
Page 80
8 Configuration WirelessHART Adapter SWA70 6. Press Apply to save the settings in the WirelessHART Adapter. – Press OK to confirm. – The event is monitored immediately if the WirelessHART Adapter is connected to the network. – If the WirelessHART Adapter is not connected to the network, a message appears to this effect.
Page 81
WirelessHART Adapter SWA70 8 Configuration Byte Meaning Process values are simulated. The hardware of the WirelessHART Adapter is defective. The hardware of the WirelessHART Adapter is defective. Software error: unexpected conditions. The voltage of the WirelessHART Adapter or the field device is too low.
The power supply parameters for the field device must be taken from the field device operating manual. For some Endress+Hauser field devices the optimum power supply parameters are provided in a database supplied with the DTM.
Page 83
WirelessHART Adapter SWA70 8 Configuration Start-up Voltage Operating Voltage Power Start-up time Lead Command 1 Command 2 Penultimate last on time time command command after external trigger device HART communication initializes additional HART synchronisation configuration time t off Fig. 8-3: Field device power parameters If the WirelessHART Adapter powers the field device as described in the section entitled "Two-wire...
Page 84
8 Configuration WirelessHART Adapter SWA70 Parameter Meaning Example Default Field Device Power Mode Specifies the power mode. Automatic • Off: no communication takes place with any connected field device. The WirelessHART Adapter acts as a router between other WirelessHART devices.
WirelessHART Adapter SWA70 8 Configuration 8.3.9 Power option The power options provide information about the power supply unit connected. 1. Click Power Option in the DTM navigation tree to display the appropriate parameters. – You can enter text in the white fields. Press Enter to save your changes.
9 Additional DTM functions WirelessHART Adapter SWA70 Additional DTM functions Offline parameterization You can configure the WirelessHART Adapter offline in the Offline Parameterization mode. See the "Opening the DTM of the WirelessHART Adapter" section on Page 62. 1. In the FieldCare network view right-click the WirelessHART Adapter and select Offline Parameterization in the context menu.
WirelessHART Adapter SWA70 9 Additional DTM functions Observing The current values and the status of the variables that were selected in the Device Variable Mapping window can be called up with the Observe function. FieldCare must be connected to the WirelessHART Adapter. In the network view right-click the WirelessHART Adapter and select Observe.
9 Additional DTM functions WirelessHART Adapter SWA70 Invoking the diagnostic parameters For the purpose of diagnostics various parameters can be called up with the Diagnosis function. In the network view right-click the WirelessHART Adapter and select Diagnosis in the context menu.
WirelessHART Adapter SWA70 9 Additional DTM functions 9.3.2 Wireless communication The Wireless Communication window contains information about the operation of the WirelessHART Adapter. This information is updated every five minutes. An explanation of the individual parameters is provided in the "Wireless communication parameters" table below.
9 Additional DTM functions WirelessHART Adapter SWA70 9.3.3 Wired communication The Wired Communication window contains information about the HART field device that is connected to the WirelessHART Adapter. An explanation of the individual parameters is provided in the "Wired communication parameters" table below.
Page 91
WirelessHART Adapter SWA70 9 Additional DTM functions Open the ASM window to see the current device health status classified according to the following scheme: • Good • Faults in the sensor or actuator element • Faults in the electronics • Installation faults, fault during start-up •...
9 Additional DTM functions WirelessHART Adapter SWA70 HART diagnosis Parameter Meaning parameters Configuration Change Counter Counts the changes in the configuration Configuration Changed Flag Flags a change in the configuration since the last communication Reboot counter Counts the number of reboots...
WirelessHART Adapter SWA70 9 Additional DTM functions Additional functions To select additional functions, in the network view right-click the WirelessHART Adapter and select Additional Functions in the context menu. 9.4.1 Simulation The Simulation function makes it possible to simulate adapter parameters. If the simulation is activated by selecting the Disabled value in the Simulation parameter, adapter variables can be chosen from a list.
9 Additional DTM functions WirelessHART Adapter SWA70 9.4.2 Access control The Lock/Unlock function allows the user to protect the WirelessHART Adapter from unauthorized access. An explanation of the individual parameters is provided in the "Access control parameters" table below. Access control parameters...
WirelessHART Adapter SWA70 9 Additional DTM functions 9.4.3 Updating the firmware The Update Firmware function allows users to download new firmware for the WirelessHART Adapter from an FTP server. To be able to do so, the Wireless Module Firmware Update Lock parameter in the Lock/Unlock window must first be set to Unlocked.
9 Additional DTM functions WirelessHART Adapter SWA70 9.4.5 Self-test The Perform Self-Test function causes the WirelessHART Adapter to perform a self-test. The result is displayed in the Diagnosis window as described in Section 9.3 "Invoking the diagnostic parameters". 9.4.6 About The About function displays information about the DTM.
"intrinsically safe power unit" version may only be replaced with the "intrinsically safe power unit" version. You can order the power supply units from your local Endress+Hauser sales partner. See the "Accessories and spare parts" section on Page 99.
In the case of devices with a battery unit, the battery unit must be removed before the device is returned. Warning! • If Endress+Hauser requests you to return the battery unit, please pay attention to the accompanying Safety Data Sheet and the local transportation conditions. 10.2.2 Disposal Dispose of the WirelessHART Adapter in accordance with the regulations that apply in your country.
Contact addresses can be found on our homepage: www.addresses.com/worldwide. If you have any questions, please contact your Endress+Hauser branch office. 10.3 Accessories and spare parts Various accessories, which can be ordered separately from Endress+Hauser, are available for the WirelessHART Adapter: • 71092238: battery unit SWA70 •...
11 Troubleshooting WirelessHART Adapter SWA70 11 Troubleshooting Error messages are displayed in the Diagnosis window of the DTM as described in the "Invoking the diagnostic parameters" section. See the "Invoking the diagnostic parameters" section on Page 88. The table below lists problems which might occur during commissioning and operation of the WirelessHART Adapter.
Page 101
WirelessHART Adapter SWA70 11 Troubleshooting Problem Solution The WirelessHART Adapter supplies power to a two- • The field device does not support the HART protocol. wire field device. The WirelessHART Adapter is – The parameters can only be read by a HART field device.
Page 102
11 Troubleshooting WirelessHART Adapter SWA70 Problem Solution The WirelessHART Adapter does not restart after • The WirelessHART Adapter shuts down when the internal disconnecting and connecting the "power" power storage units are discharged and the "power" connector. connector is plugged out.
WirelessHART Adapter SWA70 12 Technical data 12 Technical data 12.1 Input/wired interface Inputs One input channel for: • One point-to-point connection with a HART field device, or • One point-to-point connection with a 4 to 20 mA field device, or •...
12 Technical data WirelessHART Adapter SWA70 12.2 Output/wireless interface Communication interface WirelessHART communication interface Transmission rate Nominal 250 kBits/s Frequency band 2.4 GHz (ISM band) Transmission range Under reference operating conditions: outdoor 250 m (820 ft), indoor 50 m (164 ft)
WirelessHART Adapter SWA70 12 Technical data 12.3 Power supply Versions • Battery unit: special high-power lithium-thionyl battery unit, long battery life • Wide range power unit • Intrinsically safe power unit • Solar module connection Power supply • Battery unit: 5 to 7.2 V DC •...
12 Technical data WirelessHART Adapter SWA70 12.5 Environment Climate class EN 60721-3-4: 4K4H, suitable for stationary use in locations exposed to weather conditions Ambient temperature Version with battery unit: range • –40 to +80 °C/-40 to +176 °F • The battery unit capacity decreases rapidly at temperatures below –30 °C/-22 °F.
WirelessHART Adapter SWA70 12 Technical data 12.5.1 Temperature restrictions The temperature restrictions indicated are valid provided that there is a residual battery capacity of 30% or more. The tables contain the minimum operating temperatures in °C at 4 mA and 22 mA or between 4 mA and 22 mA in increments of 2 V of the field device terminal voltage.
Page 108
12 Technical data WirelessHART Adapter SWA70 Non-hazardous area version with current fixed Start-up current in mA at 4 mA See the "Field device power" section on Page 82. (multidrop mode) -40°C -40°C -40°C -40°C -40°C -40°C -40°C -40°C -40°C -40°C -40°C -40°C...
92.8 111.5 internal thread M20 x 1.5 Fig. 12-1: Housing dimensions of the WirelessHART Adapter SWA70 Weight • Without power supply unit: 0.5 kg (1.10 lbs) • With power supply unit: 0.785 kg (1.74 lbs) Material • Housing: polyester or aluminum, see ordering information •...
Can be configured via DD or DTM, default address 15 12.8 Certificates and approvals CE mark The WirelessHART Adapter SWA70 meets the legal requirements of the relevant EC guidelines. Endress+Hauser confirms that the WirelessHART Adapter SWA70 has been successfully tested by affixing to it the CE mark.
Page 111
WirelessHART Adapter SWA70 12 Technical data Telecommunication See the "Radio approvals" section on Page 9. approval • Brazil: ANATEL 2759-11-7311 (EAN Number: 7898994191421) • China: CMIIT ID (SRRC) • ETSI (R&TTE) • FCC Part 15.247 for wireless applications in the 2.4 GHz frequency band •...
Page 112
12 Technical data WirelessHART Adapter SWA70 Endress+Hauser...
Need help?
Do you have a question about the WirelessHART Adapter SWA70 and is the answer not in the manual?
Questions and answers