FieldPort SWA50 About this document About this document Document function These Operating Instructions provide all of the information that is required in various phases of the life cycle of the device including: • Product identification • Incoming acceptance • Storage •...
About this document FieldPort SWA50 Symbol Meaning … Series of steps. Result of a step. Help in the event of a problem. Visual inspection. 1.2.3 Symbols in graphics Symbol Meaning Symbol Meaning 1, 2, 3,... Item numbers … Series of steps A, B, C, ...
Registered trademark of the FieldComm Group, Austin, Texas, USA Bluetooth® The Bluetooth® word mark and logos are registered trademarks owned by the Bluetooth SIG, Inc. and any use of such marks by Endress+Hauser is under license. Other trademarks and trade names are those of their respective owners. Apple®...
Personnel follow the instructions in this manual. Designated use The FieldPort SWA50 is a loop-powered adapter that converts the HART signal of the connected HART field device into a reliable and encrypted WirelessHART signal. The FieldPort SWA50 can be retrofitted to all 2-wire or 4-wire HART field devices.
Signal transmission via Bluetooth® wireless technology uses a cryptographic technique tested by Fraunhofer AISEC. • Connection via Bluetooth® is not possible without specific Endress+Hauser devices or the SmartBlue app. • Only one point-to-point connection between one FieldPort SWA50 device and one smartphone or tablet is established.
FieldPort SWA50 and to visualize the measured values and status of the connected HART field device. HART field devices can be connected to the Netilion Cloud via the FieldPort SWA50 and a FieldEdge device. For detailed information on the Netilion Cloud, see https://netilion.endress.com...
Internet browser-based Netilion Service app or user application Endress+Hauser SmartBlue app Encrypted wireless connection via Bluetooth® HART field device with FieldPort SWA50, direct mounting HART field device with WirelessHART adapter, e.g. SWA70 Encrypted wireless connection via WirelessHART HART field device with FieldPort SWA50, remote mounting...
→ Enter serial number): All information relating to the device is then displayed. • Enter the serial number specified on the nameplate into the Endress+Hauser Operations App: All information relating to the device is then displayed. 4.2.2 Manufacturer's address Endress+Hauser SE+Co.
Fresnel zone. • Avoid mounting in close proximity to high-voltage devices. • For a better connection, mount the FieldPort SWA50 in sight of a WirelessHART FieldPort, such as the SWA50, SWA70, or a WirelessHART gateway, such as the Fieldgate SWG70.
5.2.2 "Remote mounting" version A0043240 3 Example of remote mounting FieldPort SWA50 "remote mounting" version Cable HART field device For remote mounting, we recommend the optional mounting bracket. Alternatively, you can secure the remote version using pipe clips. "Remote mounting" version of installation process: → 21 Mounting the "direct mounting"...
Page 17
• Electrical connection for 4-wire HART field devices with active current output: → 31 • Electrical connection for FieldPort SWA50 without HART field device: → 32 A0041552 Tighten screws for strain relief. Torque: 0.4 Nm ± 0.04 Nm...
Page 18
Installation FieldPort SWA50 A0041553 Slide the electronic insert into the guide inside the housing. A0040506 For information regarding torque, see the field device documentation. Endress+Hauser...
Page 19
FieldPort SWA50 Installation A0041554 Ensure that the cores are of sufficient length to be connected in the field device. Shorten the cores in the field device to the required length. A0040566 Do not tighten the top housing section yet, so that you are still able to rotate the bottom housing section.
Page 20
Installation FieldPort SWA50 A0040568 To avoid wire breaks, rotate the bottom housing section by a maximum of ± 180°. A0040569 Tighten the top housing section in such a way that it is still possible to turn the design ring. Torque: 5 Nm ± 0.05 Nm...
FieldPort SWA50 Installation A0040567 Mounting the "remote mounting" version NOTICE Damaged seal. IP degree of protection is no longer guaranteed. ‣ Do not damage seal. NOTICE Supply voltage is present during installation. Possible damage to the device. ‣ Switch off supply voltage prior to installation.
Page 22
Installation FieldPort SWA50 Mounting the FieldPort SWA50 A0040498 A0040499 A0041512 A0040500 5. If you mount the FieldPort SWA50 using the optional mounting bracket, follow the instructions in the "Mounting bracket and FieldPort SWA50" section.→ 27 Endress+Hauser...
Page 24
• Electrical connection for 4-wire HART field devices with active current output: → 31 • Electrical connection for FieldPort SWA50 without HART field device: → 32 A0040507 Tighten screws for strain relief. Torque: 0.4 Nm ± 0.04 Nm...
A0040509 Tighten the top housing section in such a way that it is still possible to turn the design ring. Torque: 5 Nm ± 0.05 Nm A0040510 Installing the FieldPort SWA50 with mounting bracket 5.5.1 Mounting and alignment options The mounting bracket can be mounted as follows: •...
Installation FieldPort SWA50 The FieldPort can be aligned as follows using the support bracket: • Via the various mounting positions on the mounting bracket • By rotating the support bracket A0043411 4 Alignment options via support bracket Various mounting positions on support bracket By rotating the support bracket 5.5.2...
Hexagonal-headed bolt for securing and grounding Support bracket Mounting bracket Round bracket If you are installing the FieldPort SWA50 using the mounting bracket, you must remove the design ring between the top housing section and the bottom housing section. Tools required •...
9. Align the transmission window of the FieldPort SWA50. 10. Tighten the top housing section. Torque: 5 Nm ± 0.05 Nm 11. Connect the protective ground to the hexagonal-headed bolt. 12. Tighten the hexagonal-headed bolt so that the FieldPort SWA50 is secured in the mounting bracket. Post-installation check Is the device undamaged (visual inspection)? ...
PLC or transmitter" electrical connection version, you can use core cross-sections of 0.75 mm² at maximum. If larger core cross-sections are required, we recommend remote mounting. Terminal assignment 1234 A0040495 8 FieldPort SWA50 terminal assignment Input terminal IN Output terminal OUT Endress+Hauser...
• Shielding: 2.5 to 6 mm (0.1 to 0.23 in) 2-wire HART field device with passive current output Some grounding concepts require shielded cables. If connecting the cable shield to the FieldPort SWA50, you must use a cable gland for shielded cable. See ordering information. Endress+Hauser...
2-wire field device 4 to 20 mA-HART 4-wire HART field device with passive current output Some grounding concepts require shielded cables. If connecting the cable shield to the FieldPort SWA50, you must use a cable gland for shielded cable. See ordering information. OUT+ –...
14 FieldPort SWA50 without HART field device (optional grounding not showing) Supply voltage of FieldPort SWA50, 10 to 30 VDC (SELV, PELV or Class 2) Electronic insert SWA50 Resistor 1.5 kOhm and min. 0.5 W between terminals OUT+ and OUT–...
The grounding clamp provided by the customer must meet the following requirements: • Diameter: approx. 40 mm • Stainless steel • If the FieldPort SWA50 is used in a hazardous area: suitable for hazardous areas as per DIN EN 62305, Sheet 3 and DIN EN 62561-1 Endress+Hauser...
Is the terminal assignment correct? Have the cables been connected in such a way that no wires, insulation and / or cable shields are jammed? Is the supply voltage correct? Is the FieldPort SWA50 grounded, if necessary? Endress+Hauser...
• Remote configuration with FieldCare SFE500 via WirelessHART Fieldgate SWG70 and DTM for FieldPort SWA50 and Fieldgate SWG70 In addition, you can connect the FieldPort SWA50 with the connected HART field device to the Netilion Cloud via the FieldEdge SGC500.
• Is there another HART master in the HART loop of the FieldPort SWA50? If yes, is it a primary or secondary HART master? • Is there a HART communication resistor ≥ 250 Ohm outside of the FieldPort SWA50 in the 4 to 20 mA loop? If yes, is the HART communication resistor connected in series between the "IN+"...
SmartBlue App. Burst message Factory configuration Every 5 minutes, the FieldPort SWA50 transmits the process values of the field device in accordance with HART command 3. Every 5 minutes, the FieldPort SWA50 transmits the diagnostic data of the field device in accordance with HART command 48.
Page 38
Example of FieldPort SWA50 with Endress+Hauser HART field device, already connected to SmartBlue App Example of FieldPort SWA50 with HART field device of another manufacturer, already connected to SmartBlue App Example of FieldPort SWA50, not yet connected to SmartBlue App...
Page 39
2. Use the "Communication resistor" parameter to check the setting for the HART communication resistor. If there is no HART communication resistor outside of the FieldPort SWA50 in the 4 to 20 mA loop, you must activate the internal HART communication resistor. → 47 3.
8.2.2 Commissioning via Field Xpert Burst messages Burst messages for the FieldPort SWA50 are configured in the factory. You can change the burst messages via WirelessHART, locally via a Commubox FXA195 using FieldCare SFE500 or via Field Xpert. Burst message...
Page 41
Reachable devices (live list) Example of FieldPort SWA50 with HART field device, never connected to Field Xpert before Example of FieldPort SWA50 with or without HART field device, already connected to Field Xpert 5. Tap the icon next to the device to be configured.
Page 42
2. Use the "Communication resistor" parameter to check the setting for the HART communication resistor. If there is no HART communication resistor outside of the FieldPort SWA50 in the 4 to 20 mA loop, you must activate the internal HART communication resistor. → 47 3.
FieldPort SWA50 Operation Operation Hardware locking The DIP switches for hardware-locking are located on the electronic insert. 1 2 3 4 1234 A0041784 20 DIP switches for hardware-locking of functions DIP switch Function Description Factory setting Bluetooth • ON: Communication via Bluetooth is communication possible, e.g.
"Device information" view – Example of SWA50 with Endress+Hauser HART field device Information about the HART field device connected to the SWA50. Firmware version, order code, device type and status are displayed only for Endress+Hauser field devices with HART 6 and HART 7. Serial number...
"Device information" view – Example of SWA50 with HART field device from another manufacturer Information about the HART field device connected to the SWA50. Firmware version, order code, device type and status are displayed only for Endress+Hauser field devices with HART 6 and HART 7. Serial number...
The "Measured values" page shows the measured values of the HART field device connected to the FieldPort SWA50. If no HART field device is connected or the HART field device is not accessible, this page shows the measured values of the FieldPort SWA50.
Page 47
Navigation: Root menu > System > FieldPort SWA50 > Connectivity > HART configuration This page is used to configure the HART parameters for the FieldPort SWA50. In addition, you can configure the HART address of the connected HART field device.
Page 48
Device revision Shows the hardware revision of the SWA50 "WirelessHART configuration" page Navigation: Root menu > System > FieldPort SWA50 > Connectivity > WirelessHART configuration This page is used to configure the WirelessHART connection. Parameter Description...
"Information" page ("Field device" menu) Navigation: Root menu > System > Field device > Information This page shows information about the HART field device connected to the FieldPort SWA50. This information is displayed for Endress+Hauser field devices with HART 6 and higher. Parameter...
– A0044191 24 Example: connection of the PC with FieldCare SFE500 via the Endress+Hauser Commubox FXA195 USB/HART modem for the electrical connection version "Electrical connection for 2-wire HART field devices with passive current output" Supply voltage or PLC with active current input or transmitter with active current input...
Page 51
FieldPort SWA50 Configuration and online parameterization Description of parameters on "Identification" page Parameter Description Long Tag Prerequisite Devices from HART version 6.0 Description Enter the name for the FieldPort. This parameter is used for the unique identification of the FieldPort in the network and in the plant.
Configuration and online parameterization FieldPort SWA50 Parameter Description Polling Address Description Enter the HART address of the FieldPort on the wired interface. User entry 0 to 63 Factory setting Additional information As the "Long Tag" and the "MAC Address" are used to identify the FieldPort in the wireless network, you can assign the same device address to different FieldPorts.
Page 53
FieldPort SWA50 Configuration and online parameterization 2. Click the >> button (Execute Join). The settings are downloaded to the FieldPort and saved. You can track the joining status in the "Join Status" parameter. Description of parameters on the "Wireless Communication" page...
Configuration and online parameterization FieldPort SWA50 Parameter Description Join Mode Description Select the event with which the FieldPort joins the network. Selection • Do not attempt to join: do not try to join the network. • Join now: the device joins the network once you click the ">> (Execute Join)"...
Page 55
FieldPort SWA50 Configuration and online parameterization Navigation Online parameterization > Wired communication Description of parameters on the "Wired Communication" page Parameter Description Polling Address Description Displays the HART address of the FieldPort. Factory setting Master Type Description Select the HART master type for the FieldPort.
Configuration and online parameterization FieldPort SWA50 Parameter Description HART Address Field Description Device Enter the HART address of the HART field device. User entry 0 to 63 Factory setting Field Device Database Description Displays the HART information of the HART field device connected to the FieldPort.
FieldPort SWA50 Configuration and online parameterization Parameter Description Select Secondary Variable Description Select the secondary variable. Selection See list. Factory setting RSL of Best Neighbor Secondary Variable Unit Description Select the unit for the secondary variable. Selection The options depend on the variable chosen.
Page 58
Burst messages for the FieldPort SWA50 – factory configuration Burst message Factory configuration Every 5 minutes, the FieldPort SWA50 transmits the process values of the field device in accordance with HART command 3. Every 5 minutes, the FieldPort SWA50 transmits the diagnostic data of the field device in accordance with HART command 48.
Page 59
FieldPort SWA50 Configuration and online parameterization 4. For the Period parameter, enter the period after which the FieldPort should send the device variables. 5. For the Burst Command Number parameter, select the number for the burst command. 6. Click the Apply button.
Page 60
Additional information Refer to the documentation of the field device for the device variables of the connected field device. Description of the burst command for the FieldPort SWA50 Burst command Description Transmits the value of the 4 to 20 mA signal and up to 4 pre-defined device variables and the associated unit.
2. On the "Event" tab, select the On option for the "Event Notification Control Code" parameter. The gray fields become white. It is possible to enter data. 3. For the Device Index parameter, select either the FieldPort SWA50 or the connected HART field device. 4. Configure the remaining parameters on the "Event" tab.
Page 62
Configuration and online parameterization FieldPort SWA50 5. On the "Standard Event Mask" tab, enable the desired event notifications by clicking the individual check box(es) in front of the event. Multiple selection is possible. 6. On the "Device-Specific Event Mask" tab, enable the desired event notifications by clicking the individual check box(es) in front of the event.
Page 63
FieldPort SWA50 Configuration and online parameterization Description of parameters for "Event Notification", "Event" tab Parameter Description Event Notification Description Control Code Enable and disable the event notification mode. Selection • Off: the event notification mode is disabled. The entry fields are grayed out and write-protected.
Page 64
Configuration and online parameterization FieldPort SWA50 Parameter Description Event Status Prerequisite Event notification: on Description Indicates whether and which event notifications have been sent and have not yet been acknowledged. If the check box is ticked, event notification has been sent but not yet acknowledged.
Page 65
Description of parameters for "Event Notification", "Device-Specific Event Mask" tab Monitoring of device-specific events • HART field device: see the Operating Instructions for the connected HART field device • FieldPort SWA50: see the following table Monitoring of standard events for FieldPort SWA50 Byte Description No join attempt started so far.
Page 66
Configuration and online parameterization FieldPort SWA50 Byte Description – – – – – – Burst or event notification exist without field device – Wired device has additional status information. Wired device is not working correctly. – – – – –...
FieldPort SWA50 Additional DTM functions Additional DTM functions 12.1 Lock / Unlock This page is used to protect the FieldPort from unauthorized access via the DTM. If the lock is activated and DIP switch 3 is set to "On", parameterization via Bluetooth is still possible.
No communication between HART Check settings of HART parameters in the FieldPort. field device and FieldPort. • SmartBlue app and FieldXpert: Root menu > System > FieldPort SWA50 > Connectivity > HART Configuration → 47 • FieldCare: Wired communication No Bluetooth communication between Check if Bluetooth communication is enabled →...
You can check the current value on the " Device information" page in the SmartBlue app. → 44 If there is no HART field device connected to the FieldPort SWA50, or if the HART field device cannot be reached, it is assumed that the loop current is sufficiently high.
Page 70
The following view is displayed: 6. Tap either the Apply button or the Later button. Apply button: The FieldPort SWA50 is restarted and the firmware update is installed on the FieldPort SWA50. Later button: The firmware update is not installed until the next time the FieldPort SWA50 is restarted.
FieldPort SWA50 Repair Repair 15.1 General notes Repairs may only be performed by Endress+Hauser staff or by individuals authorized and trained by Endress+Hauser. 15.2 Disposal If required by the Directive 2012/19/EU on waste electrical and electronic equipment (WEEE), the product is marked with the depicted symbol in order to minimize the disposal of WEEE as unsorted municipal waste.
Accessories FieldPort SWA50 Accessories Optional accessories: Mounting bracket (order number: 71487573) For detailed information about the accessories, contact your Endress+Hauser Sales Center (www.addresses.endress.com) or refer to the product page. Endress+Hauser...