40
Subscriber ID Number (Telco 2)
41
Telephone Number 2
N
:
OTE
A fixed Dial Tone Detection (E) is included prior to the Dialing Prefix (Block
Number 44). Programming an E is not required for Telco 1, Telco 2 and
Telco 3. If dial tone detection is not desired select No Dial Tone Detection
in Communicator Features (Block Number 46). Program a D if a 4 second
delay is required.
42
Receiver Format
[1]
Ademco Slow
[2]
Radionics Slow
[3]
Silent Knight Fast
[4]
Universal High Speed
[5]
Reserved
[6]
Point ID
[7]
Pager
43
Receiver Options
Default
ON
Zn 1 LED ON = 2300 Hz Handshake/Kissoff
OFF
Zn 2 LED ON = Sumcheck
OFF
Zn 3 LED ON = Single Digit
OFF
Zn 4 LED ON = No Handshake
44
Dialing Prefix
Dialing Prefix for Telco 1, Telco 2
& Telco 3.
Communicator Features 1
45
Default
ON
Zn 1 LED ON = Communicator Enabled
ON
Zn 2 LED ON = DTMF w/ Rotary Back up
OFF
Zn 3 LED ON = DTMF only
OFF
Zn 4 LED ON = Backup to Telco 2
46
Communicator Features 2
Default
(4)
OFF
Zn 1 LED ON = No Dial Tone Detection
OFF
Zn 2 LED ON = 2:1 Rotary Dialing
OFF
Zn 3 LED ON = Backup if < 4 attempts
OFF
Zn 4 LED ON = Reserved