Viking M Technical Data page 2

Quick response extended coverage light hazard extra-large orifice sprinkler
Hide thumbs Also See for M:

Advertisement

Sprin kler 71 b
Pages of the tele phone di rec tory for a lo -
cal dis trib u tor (listed un der "Sprin -
klers-Automatic-Fire") or con tact Vi king.
Vi king Tech ni cal Data may be found on
The Vi king Cor po ra tion's Web site at
http://www.vikingcorp.com.
The Web site may in clude a more re cent
edi tion of this Tech ni cal Data page.
6. GUARANTEES
For de tails of war ranty, re fer to Vi king's
cur rent price sched ule or con tact The Vi -
king Cor po ra tion di rectly.
7. INSTALLATION
WARNING: Vi king sprin klers are man u -
fac tured and tested to meet the rigid re -
quire ments of the ap prov ing agency.
The sprin klers are de signed to be in -
stalled in ac cor dance with rec og nized
in stal la tion stan dards. De vi a tion from
the stan dards or any al ter ation to the
sprin kler af ter it leaves the fac tory in -
clud ing, but not lim ited to: paint ing, plat -
ing, coat ing, or mod i fi ca tion, may ren der
the sprin kler in op er a tive and will au to -
mat i cally nul lify the ap proval and any
guar an tee made by The Vi king Cor po ra -
tion.
A. Sprin klers are to be in stalled in ac cor -
dance with the lat est pub lished stan -
dards of the Na tional Fire Pro tec tion
As so ci a tion, Fac tory Mu tual, Loss
Pre ven tion Coun cil, Assemblee
P l e n i e r e ,
V e r b a n d
Sachversicherer or other sim i lar or -
ga ni za tions, and also with the pro vi -
sions of gov ern men tal codes, or di -
nances, and stan dards when ever ap -
pli ca ble. The use of QR-ECLH-ELO
Sprin klers may be lim ited due to oc -
cu pancy and haz ard. Re fer to the Au -
thor ity Hav ing Ju ris dic tion prior to in -
stal la tion.
B. Sprin klers must be han dled with care.
They must be stored in a cool, dry
place in their orig i nal ship ping con -
tainer. Never in stall sprin klers that
have been dropped or dam aged in
any way. Never in stall any glass-bulb
sprin kler if the bulb is cracked or if
there is a loss of liq uid from the bulb.
If a glass bulb lacks the ap pro pri ate
amount of fluid, it should be set aside
and re turned to Vi king (or an au tho -
rized Vi king dis trib u tor) for anal y sis
as soon as pos si ble. If the sprin kler is
not re turned to Vi king, it should be
de stroyed. Never in stall sprin klers
which have been ex posed to tem per -
a tures in ex cess of the max i mum am -
bi ent tem per a ture al lowed (these
sprin klers should be de stroyed im -
me di ately).
TECH NI CAL DATA
C. Cor ro sion-resistant sprin klers must
be in stalled when sub ject to cor ro -
sive at mo spheres. When in stall ing
sprin klers with a cor ro sion-resistant
coat ing, care must be taken not to
dam age the coat ing. Use only the
spe cial wrench de signed for in stall -
ing coated and re cessed Vi king ELO
sprin klers. (Any other wrench may
dam age the coat ing.)
D. The sprin klers must be in stalled af ter
the pip ing is in place to pre vent me -
chan i cal dam age. Be fore in stal la tion,
be sure to have the ap pro pri ate sprin -
kler model and style, with the cor rect
or i fice size, tem per a ture rat ing, and
re sponse char ac ter is tics.
1. In stall es cutch eon (if used), which
is de signed to thread onto the ex -
ter nal threads of the sprin kler.
2. Ap ply a small amount of pipe-joint
com pound or tape to the ex ter nal
threads only, tak ing care not to al -
low a build-up of com pound in side
the sprin kler in let.
3. In stall the sprin kler on the pip ing
us ing the spe cial sprin kler wrench
only, tak ing care not to dam age
the sprin kler op er at ing parts. DO
NOT use the sprin kler de flec tor to
start or thread the sprin kler into a
fit ting.
E. Af ter in stal la tion, the en tire sprin kler
sys tem must be tested in ac cor dance
with the rec og nized in stal la tion stan -
d e r
dards. The test is ap plied af ter the
sprin kler in stal la tion to en sure that no
dam age has oc curred to the sprin kler
dur ing ship ping and in stal la tion, and
to make sure the sprin kler has been
prop erly tight ened. If a thread leak
oc curs, nor mally the sprin kler must
be re moved, new pipe-joint com -
pound or tape ap plied, and then re in -
stalled. This is due to the fact that
when the joint seal is dam aged, the
seal ing com pound or tape is washed
out of the joint. Air test ing the sprin -
kler pip ing prior to test ing with wa ter
may be con sid ered in ar eas where
leak age dur ing test ing must be pre -
vented. Re fer to the In stal la tion
Guides and the Au thor ity Hav ing Ju -
ris dic tion.
F. Sprin klers must be pro tected from
me chan i cal dam age. Wet pipe sys -
tems must be pro vided with ad e -
quate heat. When in stall ing Model M
QR-ECLH-ELO Sprin klers on dry
sys tems, re fer to the In stal la tion
Guides and the Au thor ity Hav ing
Ju ris dic tion.
8. MAINTENANCE
NO TICE: The owner is re spon si ble for
main tain ing the fire-protection sys tem
MODEL M QUICK RE SPONSE
EX TENDED COV ER AGE
LIGHT HAZ ARD
EX TRA-LARGE OR I FICE SPRIN KLER
and de vices in proper op er at ing con di -
tion. For min i mum main te nance and in -
spec tion re quire ments, re fer to the Na -
tional Fire Pro tec tion As so ci a tion's
pam phlet that de scribes care and main -
te nance of sprin kler sys tems. In ad di -
tion, the Au thor ity Hav ing Ju ris dic tion
may have ad di tional main te nance, test -
ing, and in spec tion re quire ments that
must be fol lowed.
A. Sprin klers must be in spected on a
reg u lar ba sis for cor ro sion, me chan i -
cal dam age, ob struc tions, paint, etc.
The fre quency of the in spec tions
may vary due to cor ro sive at mo -
spheres, wa ter sup plies, and ac tiv ity
around the de vice.
B. Sprin klers that have been field
painted or me chan i cally dam aged
must be re placed im me di ately.
Sprin klers show ing signs of cor ro -
sion shall be tested and/or re placed
im me di ately as re quired. In stal la tion
stan dards re quire sprin klers to be
tested and, if nec es sary, re placed
im me di ately af ter a spec i fied term of
s e r v i c e . F o r V i king M o d e l M
QR-ECLH-ELO Sprin klers, re fer to
the In stal la tion Stan dards and the
Au thor ity Hav ing Ju ris dic tion for the
spec i fied pe riod of time af ter which
test ing and/or re place ment is re -
quired. Sprin klers that have op er ated
can not be re as sem bled or re-used,
but must be re placed. When re plac -
ing sprin klers, use only new sprin -
klers.
C. The sprin kler dis charge pat tern is crit -
i cal for proper fire pro tec tion. Noth ing
should be hung from, at tached to, or
oth er wise ob struct the dis charge pat -
tern. All ob struc tions must be im me -
di ately re moved or, if nec es sary, ad -
di tional sprin klers in stalled.
D. When re plac ing ex ist ing sprin klers,
the sys tem must be re moved from
ser vice. Re fer to the ap pro pri ate sys -
tem de scrip tion and/or valve in struc -
tions. Prior to re mov ing the sys tem
from ser vice, no tify all Au thor ities
Hav ing Ju ris dic tion. Con sid er ation
should be given to em ploy ment of a
fire pa trol in the af fected area.
1. Re move the sys tem from ser vice,
drain all wa ter, and re lieve all
pres sure on the pip ing.
2. Using the spe cial sprin kler wrench,
re move the old sprin kler and in -
stall the new unit. Care must be
taken to en sure that the re place -
ment sprin kler is the proper model
and style, with the cor rect or i fice
size, tem per a ture rat ing, and re -
sponse char ac ter is tics. A fully
stocked spare sprin kler cab i net
June 4, 1999