The Indoor Unit Installation; Indoor Unit Drain Piping - LG ATNQ36GNLE7 Installation Manual

Hide thumbs Also See for ATNQ36GNLE7:
Table of Contents

Advertisement

Available languages

Available languages

Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
The following parts is option.
① Hanging Bolt
- W 3/8 or M10
② Nut
- W 3/8 or M10
③ Spring Washer - M10
④ Plate Washer - M10
Drill the piping hole on the wall slightly tilted
to the outdoor side using a Ø 70 mm
hole-core drill.
Keep the length of the bolt
from the bracket to 40mm
Ceiling board
Keep the length of 15~18 mm
between the air conditioner
bottom surface and the ceiling
surface.
Paper model
for installation
Adjust the
same height
!
CAUTION
Tighten the nut and bolt to prevent unit
falling.
Wall
Indoor
Flat washer for M10
(accessory)
Flat washer for M10
(accessory)
Nut
(W3/8 or M10)
Ceiling
Air Conditioner
body
Ceiling
board
Set screw of paper
model (4 pieces)
Open the ceiling board
along the outer edge of
the paper model
Outdoor

THE INDOOR UNIT INSTALLATION

Indoor Unit Drain Piping

- Drain piping must have down-slope (1/50 to
1/100): be sure not to provide up-and-down
slope to prevent reversal flow.
- During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
- The outside diameter of the drain connection
on the indoor unit is 32mm.
Piping material: Polyvinyl chloride pipe VP-
25 and pipe fittings
- Be sure to execute heat insulation on the
drain piping.
- Install the drain raising pipes at a right
angle to the indoor unit and no more than
300mm from the unit.
Pipe clamp
Indoor unit
Maintenance
drain port
300mm or less
300mm or less
Clamp metal(attached)
Heat insulation material: Polyethylene
foam with thickness more than 8mm.
9
Upward
routing
not allowed
1 -1.5m
Drain raising pipe
Drain hose(attached)