7
TEACHING MODE
● Be sure that detection may become unstable depending on the use environ-
ment in teaching if less margin is applied.
● When teaching in Window comparator mode or Hysteresis mode, a setting
has to be made in PRO mode beforehand.
In case 1-point teaching, make sure to set the shift amount. (initial value is
10% or 100)
For the setting, refer to "PRO MODE OPERATION MANUAL."
● Teaching can be set in RUN mode.
Useful when sensing object can be set
● This is basic teaching method.
2-point teaching
<Thru-beam type>
1
2
1. Press the SET key in the sensing object present condition.
2. Press the SET key in the sensing object absent condition.
Stable sensing is possible
Stable sensing is not possible
Useful when sensing object cannot be set
● This is teaching method in case small object or object in back ground are existing
Limit-teaching
<Thru-beam type and refractive type are common>
or
Note: The shift value of approx. 15% is an initial value. Display of the shift value can be changed to percentage
[approx. 0 to 999% (unit 1 %)] or incident light intensity [0 to 9999 (unit 1)].
For setting the shift amount, refer to "PRO MODE OPERATION MANUAL."
Useful when not want to stop production line and to keep the sensing object move
Full-auto teaching
<Thru-beam type and refractive type are common>
1. Pressing SET key down
Pressing down long
2. Run the sensing object on the line and hold down the SET key.
3. "
" is displayed on the digital display (green) and when the
sensing object passed through, release the SET key.
Automatic
Stable sensing is possible
Stable sensing is not possible
<Reflective type>
1
2
1. Press the SET key in the sensing
object present condition or non
sensing object present condition.
2. The threshold level is shifted to
high value (low sensitivity) by
pressing down UP key.
The threshold level is shifted to low
value (high sensitivity) by pressing
down UP key.
Stable sensing is possible
Stable sensing is not possible
1-point teaching (Window comparator mode / Hysteresis mode)
● This is method to set the shift amount to the desired value and to set the
threshold range by using the 1-point teaching.
<Window comparator mode>
Set to de-
Set to de-
sired value
sired value
1_SL
P-1
2_SL
1. Pressing SET key down
2. Press the SET key down in the sensing object present condition.
3. The threshold value (1_SL) that is 10% lower from the incident
light intensity and the threshold value (2_SL) that is 10% higher
from the incident light intensity are set. (Note 1, 2)
Stable sensing is possible
Stable sensing is not possible
Notes 1) The shift amount of 10% is an initial value. The shift amount can be set in PRO mode. Furthermore, the shift
value can be set in incident light amount. For setting method, refer to "PRO MODE OPERATION MANUAL."
2) If the value after setting exceeds the maximum (minimum), the maximum (minimum) sensitivity will be set.
2-point teaching (Window comparator mode / Hysteresis mode)
● This is method to set the threshold range by conducting the 2-point teaching (P-1, P-2).
● When conducting teaching, use sensing objects (P-1 and P-2) whose incident
light intensities are different from each other.
<Window comparator mode>
1_SL (P-1)
2_SL (P-2)
1. Pressing SET key down (1st time)
2. Press down the SET key in the sensing object present condition.
(2nd time)
Stable sensing is possible
Stable sensing is not possible
Note: If the value after setting exceeds the maximum (minimum), the maximum (minimum) sensitivity will be set.
3-point teaching (Window comparator mode / Hysteresis mode)
● This is the method to conduct the 3-point teaching (P-1, P-2, P-3) and to set the
threshold range by setting the threshold value (1_SL) of the mid-point between "A"
and "B" and the threshold value (2_SL) of the mid-point between "B" and "C".
● When conducting teaching, use sensing objects (A, B and C) whose incident
light intensities are different.
● After teaching, P-1, P-2 and P-3 will be automatically relocated in ascending order:
i.e. the lowest value is placed in "A", the second lowest in "B" and the highest in "C".
<Window comparator mode>
A
1_SL
B
2_SL
1. Press SET key down in the sensing object present condition (1st time)
2. Press SET key down in the sensing object present condition (2nd time)
3. Press SET key down in the sensing object present condition (3rd time)
Stable sensing is possible
Stable sensing is not possible
Note: If the value after setting exceeds the maximum (minimum), the maximum (minimum) sensitivity will be set.
Span adjustment in rising differential mode or trailing differential mode
● Press the SET key to confirm the setting item.
● The threshold can be set by using the threshold value fine adjustment function.
For the threshold value fine adjustment function, refer to "
VALUE FINE ADJUSTMENT FUNCTION"
Changed intensity
<Hysteresis mode>
Set to de-
Set to de-
sired value
sired value
1_SL
P-1
2_SL
<Hysteresis mode>
1_SL (P-1)
2_SL (P-2)
<Hysteresis mode>
C
A
1_SL
B
2_SL
THRESHOLD
Short span
Long span
C