Installer Settings Menu - Daikin D2C24ND035A5AA Operation Manual

Wall-mounted condensing boiler
Hide thumbs Also See for D2C24ND035A5AA:
Table of Contents

Advertisement

Available languages

Available languages

#
Description
U06
Set value for the room
thermostat at reduced mode
U07
Set value for the flow
temperature at day mode
U08
Set value for the flow
temperature at reduced mode
U09
Domestic hot water comfort
mode user record dependency
U10
Room temperature setpoint
used by Daikin room thermostat
during night
(a)
t00
Year
(a)
t01
Mounth
(a)
t02
Day
(a)
t03
Hour
(a)
t04
Minute
(a)
Applicable if energy metering is enabled.
User settings menu: Parameters (detailed)
#
U00
When using outdoor sensor, above this parameter
value of outside temperature, the boiler senses the
season as summer and does not activate central
heating although there is demand. Summer-winter
switching has a hysteresis of ±1ºC.
i.e: When this parameter is adjusted to 20ºC, the boiler
switches to summer mode at 21ºC and switches back
to winter mode at 19ºC.
U01
This value is used when only outside sensor is
connected to the boiler (No Opentherm room
thermostat connection). The parameter heating slope is
important to adapt the weather compensation to the
individual heating system, the building and the thermal
insulation. The heating slope can be adjusted from 0
to 40. The heating slope needs to be increased to
increase the boiler central heating set temperature.
Colder regions require a higher heating slope value.
Note: To activate weather compensation, the heating
slope value must be higher than "5".
U02
Enabling / disabling central heating ECO mode.
1 = enabled, 0 = disabled
U03
Enabling / disabling domestic hot water comfort mode.
1 = enabled, 0 = disabled
U04
Domestic hot water set value (same function that can
be done via the right dial when domestic hot water
mode is enabled).
U05
When On-Off room thermostat and outdoor sensor are
both connected, this parameter value is the virtual room
temperature setpoint when there is a heat demand.
U06
When On-Off room thermostat and outdoor sensor are
both connected, this parameter value is the virtual room
temperature setpoint when there is no heat demand.
Note: For this parameter value to be active, reducing
mode has to be enabled by your service agent,
otherwise central heating mode will not be activated
when there is no heat demand.
U07
When On-Off room thermostat is connected and
outdoor sensor is not connected, this parameter value
is the central heating water temperature setpoint when
there is a heat demand.
D2C20ND028A5AA + D2C24ND035A5AA
Wall-mounted condensing boiler
3P469438-10H – 2018.05
Unit Default Range
°C
18
10~30
°C
50
30~80
°C
35
30~80
1
1, 2 or
24
°C
18
10~30
1~99
1~12
1~31
0~23
0~59
Description
#
U08
When On-Off Room thermostat is connected and
outdoor sensor is not connected, this parameter value
is the central heating water temperature setpoint when
there is not a heat demand.
Note: For this parameter value to be active, reducing
mode has to be enabled by your service agent,
otherwise central heating mode will not be activated
when there is no het demand.
U09
If parameter is 1, comfort mode preheating will depend
on the user record. It will preheat the water according to
the previous day user records.
If parameter is 2, comfort mode preheating will be
independent of the user record, and at the highest
comfort level (3-star comfort according to EN 13302).
If parameter is 24, comfort mode preheating will be
independent of the user record.
Note: If you increase the comfort level, the energy
consumption increases.
U10
Room temperature setpoint used by Daikin Opentherm
room thermostat during night mode. Only visible in case
Daikin Opentherm room thermostat is connected.
(a)
t00
The date and time are set by means of t parameters to
update the LAN adapter. This is needed in case the
(a)
t01
LAN adapter does not have internet connection.
(a)
t02
Time and date settings is saved when menu is quitted
(a)
t03
by pressing (back) button.
(a)
t04
After date and time are set, UH-08 error disappears.
(a)
Applicable if energy metering is enabled.
To use the user settings menu
1 Press the "Enter" button when the
menu level 1 screen.
Result: You can see the parameter values on menu level 2.
2 Select U or t parameters with the left dial.
3 Select the index with the right dial.
4 Press the "Enter" button when the parameter that you want to
change is displayed.
Result: You can see the menu level 3 screen. Up and down
arrows will appear.
5 Change the parameter with the right dial.
6 Press the "Enter" button to confirm or the "Cancel" button to
cancel. You will return to menu level 2 after pressing "Enter" or
"Back"
3.5.4

Installer settings menu

Only qualified persons are allowed to enter the installer settings
menu.
3 Operation
Description
icon is displayed on the
Operation manual
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

D2c20nd028a5aaD2hnd-a5aD2cnd-a5a

Table of Contents