Mitsubishi PUMY-P100VHM Technical & Service Manual page 55

Table of Contents

Advertisement

9-5. INTERNAL SWITCH FUNCTION TABLE
PUMY-P100VHM
PUMY-P100VHMA
PUMY-P100VHMA-BS PUMY-P125VHMA-BS
Switch
Step
SWU1
1st digit
SWU2
2nd digit
SW1 Digital
Display
1~8
Switching
Selects operating system startup
1
Connection Information Clear Switch
2
3
Abnormal data clear switch input
SW2
Function
4
Pump down
Switching
5
Auto change over from Remote controller
6
1
ON/ OFF from outdoor unit
SW3 Trial
operation
2
Mode setting
SW4
Model
1~6
Switching
Pressure limitation value change
1
Change the indoor unit's LEV opening at
2
start
Fixing the indoor units linear expansion
3
SW5
valve opening
Function
Fix the operation frequency
4
switching
Change the indoor unit's LEV opening
5
at defrost
Switching the target sub cool.
6
During the FAN or COOL mode, and thermo-OFF
7
or stop in heating operation, set the opening of
linear expansion valve on indoor unit 1
During the FAN or COOL mode, and thermo-OFF
8
in heating operation, set the opening of linear ex-
pansion valve on indoor unit 2
1 SW5-7 Refrigerant shortage amount is measured during heating operation.
(Refrigerant piping is long etc.)
2 SW5-8 Countermeasure against room temperature rise for indoor unit in FAN, COOL, and thermo-OFF (heating) mode.
PUMY-P125VHM
PUMY-P125VHMA
Function
0
SWU2
(2nd digit)
ON
OFF
1
2 3 4 5 6 7 8
SW4
MODELS
ON
PUMY-P100
OFF
1 2 3 4 5 6
ON
PUMY-P125
OFF
1 2 3 4 5 6
ON
PUMY-P140
OFF
1 2 3 4 5 6
PUMY-P140VHM
PUMY-P140VHMA
PUMY-P140VHMA-BS
Operation in Each Switch Setting
ON
OFF
0
SWU1
(1st digit)
With centralized
Without centralized
controller
controller
Clear
Do not clear
Clear abnormal data
Normal
Normal
Run adjustment mode.
Disable
Enable
ON
OFF
Heating
Cooling
Enable
Normal
Enable
Normal
Fix
Normal
Fix
Normal
Enable
Normal
Enable
Normal
Active
Inactive
Active
Inactive
55
When to Set
<Initial Setting>
0
Before turning
the power on
SWU2
(2nd digit)
Can be set
<Initial Setting>
either during
ON
operation or not.
OFF
1
<Initial Setting>
Before turning the
power on
ON
OFF to ON any time after
the power is turned on.
OFF
During compressor
1
running
Before turning
the power on
<Initial Setting>
Any time after the
power is turned on.
<Initial Setting>
Set for each capacity.
Before the power
is turned on.
<Initial Setting>
Can be set when off
or during operation
ON
OFF
1
OFF to ON during com-
pressor running.
Can be set when off
or during operation
Remarks
0
SWU1
(1st digit)
2 3 4 5 6 7 8
2 3 4 5 6
ON
OFF
1
2
2 3 4 5 6 7 8

Advertisement

Table of Contents
loading

Table of Contents