5-3. CORRECTING COOLING AND HEATING CAPACITY
5-3-1. Correcting Capacity for Changes in Air Conditions
(1)The performance curve charts (Figure 1, 2) show the change ratio of capacity and input (power consumption) according to the
indoor and outdoor temperature condition when defining the rated capacity (total capacity) and rated input under the standard
condition in standard piping length (5m) as "1.0".
• Standard conditions:
• Use the rated capacity and rated input given in "5-2.".
• The input is the single value of the outdoor unit; the input of each indoor unit must be added to obtain the total input.
(2)The capacity of each indoor unit may be obtained by multiplying the total capacity obtained in (1) by the ratio between the
individual capacity at the rated time and the total capacity at the rated time.
Individual capacity under stated conditions = total capacity under the stated conditions o
(3)Capacity correction factor curve
Figure 1. PUMY-P100VHM PUMY-P100VHMA PUMY-P100VHMA-BS
PUMY-P125VHM PUMY-P125VHMA PUMY-P125VHMA-BS
PUMY-P140VHM PUMY-P140VHMA PUMY-P140VHMA-BS
Cooling performance curve
1.4
Cooling
Capacity
1.2
(ratio)
1.0
0.8
0.6
1.4
Cooling
Power
1.2
consumption
(ratio)
1.0
0.8
0.6
0.4
-5 0
10
Outdoor <D.B. :>
Indoor
Rated cooling capacity
Outdoor D.B. 35°C
Indoor
Rated heating capacity
Outdoor D.B. 7°C / W.B. 6°C
22
20
18
16
INDOOR
<W.B. :>
22
20
18
16
INDOOR
<W.B. :>
20
30
40 46
D.B. 27°C / W.B. 19°C
D.B. 20°C
Figure 2. PUMY-P100VHM PUMY-P100VHMA PUMY-P100VHMA-BS
PUMY-P125VHM PUMY-P125VHMA PUMY-P125VHMA-BS
PUMY-P140VHM PUMY-P140VHMA PUMY-P140VHMA-BS
Heating performance curve
1.4
Heating
Capacity
1.2
(ratio)
1.0
0.8
0.6
0.4
Heating
Power
1.4
consumption
(ratio)
1.2
1.0
0.8
0.6
0.4
-15
15
individual capacity at the rated time
total capacity at the rated time
-10
-5
0
5
10
Outdoor <W.B. :>
15
20
25
INDOOR
<D.B. :>
INDOOR
<D.B. :>
20
15
25
15

Advertisement

Table of Contents
loading

Table of Contents