OPERATING PROCEDURE
11. Removing bypass valve coil (SV) and bypass valve
(only PUHZ-HRP·V/YHA, PUHZ-HRP·V/YHA2)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Remove 3 right side panel fixing screws (5 × 12) in the
rear of the unit and remove the right side panel.
(4) Remove the bypass valve solenoid coil fixing screw (M5
× 6).
(5) Remove the bypass valve coil by sliding the coil upward.
(6) Disconnect the connector SV2 (blue) on the controller cir-
cuit board in the electrical parts box.
(7) Recover refrigerant.
(8) Remove the welded part of bypass valve.
Note 1: Recover refrigerant without spreading it in the
air.
Note 2: The welded part can be removed easily by
removing the right side panel.
12. Removing the reactor (DCL) and capacitor (CB)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Remove the electrical parts box. (See Photo 3)
[Removing the reactor]
(4) Remove 4 reactor fixing screws (4 × 10) and remove the
reactor.
[Removing the capacitor]
(4) Remove 2 capacitor band fixing screws (4 × 10) and
remove the capacitor.
w The reactor and capacitor are attached to the rear of the
electrical parts box.
13. Removing the pressure sensor (63HS) (HRP71/100VHA2)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Pull out the lead wire of pressure sensor.
(4) Recover refrigerant.
(5) Remove the welded part of pressure sensor.
Note 1: Recover refrigerant without spreading it in the
air.
Note 2: The welded part can be removed easily by
removing the right side panel.
Note 3: When installing the pressure sensor, make
sure to cover it with a wet cloth to prevent it
from heating (100°C or more), then braze the
pipes so that the inside of pipes are not oxi-
dized.
OCH425D
Photo 10
Bypass valve
coil fixing screw
Replace filter
Bypass valve coil (SV)
Photo 11
Reactor
(DCL)
Reactor
fixing
screws
Capacitor (CB)
LEV coil (LEV-C)
Figure 3
High pressure
switch (63L)
4-way
valve coil (21S4)
4-way valve
Pressure
sensor (63HS)
110
PHOTOS
Thermistor
<Outdoor pipe>
(TH33)
Bypass valve
Electrical parts box
Reactor
fixing
screws
Capacitor band
fixing screws
LEV
LEV coil (LEV-A)
Thermistor
<outdoor pipe> (TH33)
Bypass valve coil (SV)
(except HRP·HA2R1/R2)
Bypass valve
(except HRP·HA2R1/R2)
LEV
LEV coil (LEV-B)
Low pressure
switch (63L)