Mitsubishi Electric MSZ-AP15VG-E1 Service Manual page 23

Hide thumbs Also See for MSZ-AP15VG-E1:
Table of Contents

Advertisement

2. Table of indoor unit failure mode recall function
Left lamp of OP-
Abnormal point
ERATION INDICA-
(Failure mode)
TOR lamp
Not lit
Normal
1-time blink every
Room temperature
0.5-second
thermistor
Indoor coil
2-time blink
2.5-second OFF
thermistor
3-time blink
Serial signal
2.5-second OFF
11-time blink
Indoor fan motor
2.5-second OFF
12-time blink
Indoor control
2.5-second OFF
system
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-4.).
OBH838B
Condition
The room temperature thermistor short or
open circuit is detected every 8 seconds dur-
ing operation.
The indoor coil thermistor short or open circuit
is detected every 8 seconds during operation.
The serial signal from outdoor unit is not re-
ceived for a maximum of 6 minutes.
The rotational frequency feedback signal is not
emitted during the 12 seconds the indoor fan
operation.
It cannot properly read data in the nonvolatile
memory of the indoor electronic control P.C.
board.
23
Remedy
Refer to the characteristics of the room temperature
thermistor (10-7.).
Refer to the characteristics of the main indoor coil ther-
mistor, the sub indoor coil thermistor (10-7.).
Refer to 10-6.
"How to check miswiring and serial
signal error".
Refer to 10-6.
"Check of indoor fan motor".
Replace the indoor electronic control P.C. board.