Note: The following battery replacement instructions are for Tripp Lite RBCSUT Replacement Batteries Cartridges.
1
Make sure the DC breaker is tripped (set to off, or the "O" position).
2
Open the battery pack's front door.
3
Open the terminal housings covering the internal battery cable
terminals. Disconnect the terminals (Figure 3-1). Refer to Figure
3-2 for the entire battery installation.
4
Remove the screws securing the wiring brackets. Remove
brackets.
Carefully remove each used battery string by pulling it out by
5
its tab. Insert the new battery string into the slot.
Use the screws from step 4 to reattach the wiring brackets.
6
In the reverse order of step 3 (4,3,2,1), reconnect the
7
battery terminals. Refer to Figure 3-2 for the entire battery
installation.
Important! Make sure all cables labeled with a +, -,
or N are correctly connected to their corresponding
connector. Improper connection can result in damage
to battery pack and/or UPS system. Please refer to the
white labels attached to the cables and the labels on
the terminal housings for proper connection.
Once all connectors are attached, close the terminal
housings.
Set the DC breaker to the on ("I") position to resume
8
normal operation.
3
–1
through
–4
N1
through
N4
3
1. Disconnect the +1, +2, +3 and +4 cables on the right.
2. Disconnect the -1, -2, -3 and -4 cables on the left.
3. Disconnect the N1, N2, N3 and N4 cables in the center.
4
8
Figure 3-1
+1
through
+4