Connecting a UPS to the Battery Pack
The external battery pack will increase the battery runtime. As a result, recharge time will also increase. Follow the installation diagram below
to connect the battery pack to the UPS. For information on connecting to the UPS terminal block, refer to sections 3.6.2 and 3.7 of the
SUT UPS Owner's Manual.
UPS System
Battery Input Cable*
* Use copper wire rated to 194°F (90°C) or higher. If using cable designed for a lower temperature capacity, please size wire according to local regulations.
TO ADDITIONAL
EXTERNAL BATTERY
PACK (NO WIRE
CONNECTION
OTHERWISE)
Notes:
• The DC breaker is tripped (set to off, or the "O" position) at the factory. Do not flip the breaker's actuator lever to the on ("I") position until the battery pack
has been properly connected to the UPS.
• Always use compression lugs with cabling to connect the UPS to the battery pack's terminal block.
• Installer should determine correct wire type based on application.
SUT20K
SUT30K
2
1 AWG (35 mm
)
1/0 AWG (50 mm
+ +
N
SUT40K
2
)
3/0 AWG (95 mm
N
6
SUT60K
2
)
250 kcmil (120 mm
TO UPS
2
)