9-7. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS
(1) Function of switches
PUHZ-W85VAA.UK
PUHZ-W85YAA.UK
Type
No.
Function
of
Switch
switch
1
Manual defrost *
2
Abnormal history clear
3
4
Refrigerant address
setting
SW1
DIP
5
switch
6
1
No function
SW4
2
No function
1
No function
SW8
2
No function
Separate indoor/outdoor
3
unit power supplies
*
1
Manual defrost should be done as follows.
1 Change the DIP SW1-1 on the outdoor controller board from OFF to ON.
2 Manual defrost will start by the above operation 1 if all these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor started operating or previous manual defrost finished.
• Pipe temperature is less than or equal to 8:.
Manual defrost will finish if certain conditions have been satisfied.
Manual defrost can be done if above conditions have been satisfied when DIP SW1-1 is changed from OFF to ON.
After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again. This
depends on the service conditions.
OCH681
PUHZ-W112VAA.UK
PUHZ-W112YAA.UK
Action by the switch operation
ON
1
Start
Clear
ON
ON
1 2 3
4 5 6
1 2 3 4 5 6
0
1
ON
ON
1 2 3
4 5 6
1 2 3 4 5 6
4
5
Used
OFF
Normal
Normal
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
2
3
Not used
40
Effective timing
When compressor is working
in heating operation.*
off or operating
When power supply ON
When power supply ON
Continue to the next page