Mitsubishi Electric PUHZ-W85VAA Service Manual page 30

Air to water heat pump units
Hide thumbs Also See for PUHZ-W85VAA:
Table of Contents

Advertisement

Check method of DC fan motor (fan motor/outdoor controller circuit board)
Notes
1
· High voltage is applied to the connector (CNF1) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNF1) for the motor with the power supply on.
(It causes trouble of the outdoor controller circuit
Self check
2
Symptom: The outdoor fan cannot rotate.
Fuse check
Check the fuse (F5) on outdoor
controller board.
Did the fuse blow?
No
Wiring contact check
Contact of fan motor connector (CNF1)
Is there contact failure?
No
Fan motor check (CNF1)
Is the resistance abnormal?
No
Power supply check (Remove the connector (CNF1))
Measure the voltage in the outdoor controller circuit
TEST POINT
1 : V
(between 1 (+) and 4 (−) of the fan connector): V
DC
TEST POINT
2 : V
(between 5 (+) and 4 (−) of the fan connector): V
CC
Is the voltage normal?
No
Replace outdoor
controller board.
Check the operation.
Fail
Replace the defective fan motor.
9-5. HOW TO CHECK THE COMPONENTS
<HIGH PRESSURE SENSOR>
Vout (V)
4.5
2.5
0.5
OCH681
Replace the outdoor controller board (C.B)
Yes
and the defective fan motor (MF1).
UNIT
FAN MOTOR
BH61J064
Measuring points
Resistance
pin1–pin4
1.1MΩ
pin5–pin4
pin6–pin4
pin7–pin4
Replace the defective fan motor.
Yes
board.
Replace the defective fan motor.
Yes
OK
Replace the outdoor controller board.
END
PRESSURE
2.5
5
(MPaG)
(PSI)
board and fan motor.)
W85
W112
BH61J065
Resistance
1.1MΩ
40kΩ
40kΩ
280–380 V DC
DC
15 V DC
CC
Yes
Check the operation of fan.
Fail
MULTI
CONTROLLER BOARD
5 V DC
3
WT
2
BU
Vout
1
BK
63HS
3-1 : 5 V (DC)
2-1 : Output Vout (DC)
30
OK
END
MICRO
PROCESSOR
GND