Maintenance Owner/Operator Can Perform - Generac Power Systems 004991-0 Owner's Manual

Liquid-cooled, prepackaged standby generators
Table of Contents

Advertisement

Figure 4.1 - Oil Dipstick and Oil Fill Cap
Oil Dipstick
Oil Filter
4.4.2 BATTERY FLUID
Check battery electrolyte fluid at least once weekly.
Fluid should cover separators in all battery cells. If
fluid level is low, add distilled water to cover tops of
separators. DO NOT USE TAP WATER IN BATTERY.
4.4.3 ENGINE COOLANT
Check coolant level in coolant recovery bottle. See
Specifications, Section 1.10.
• Add recommended coolant mixture as necessary.
• Periodically remove radiator pressure cap to make
sure the coolant recovery system is functioning
properly. Coolant should be at bottom of radiator
filler neck. If coolant level is low, inspect gasket in
radiator pressure cap. Replace cap, if necessary.
To have pressure cap tested, contact an authorized
Generac Service Dealer. Inspect cooling system
and coolant recovery system for leaks.
4.5
MAINTENANCE OWNER/
OPERATOR CAN PERFORM
4.5.1 CHECK ENGINE OIL LEVEL
Refer to "Checking Fluid Levels" in Section 4.4.
4.5.2 CHECK BATTERY
• Check battery fluid level each week as outlined
under "Check Fluid Levels".
• Check battery cables for condition, tightness, cor-
rosion or damage. Clean, tighten or replace as
necessary.
4.5.3 EXERCISE SYSTEM
Start the generator engine at least once every seven
days and let it run at least 20 minutes. See Section
3.6, "Weekly Exercise Cycle".
16 Generac
®
Power Systems, Inc.
Section 4 — Maintenance
Generac Liquid-cooled Generators
Oil Fill
4.5.4 INSPECT COOLING SYSTEM
• Inspect engine cooling system at least once each
month.
• Check hoses for damage, deterioration, leaks, etc.
Correct any discrepancies found.
• Check hose clamps for tightness.
4.5.5 CHECK ENGINE COOLANT LEVEL
See "Checking Fluid Levels" in Section 4.4.
4.5.6 PERFORM VISUAL INSPECTION
Complete a thorough visual inspection of the entire
engine-generator monthly. Look for obvious damage,
loose, missing or corroded nuts, bolts and other fas-
teners. Look for fuel, oil or coolant leaks.
4.5.7 INSPECT EXHAUST SYSTEM
Inspect the exhaust system at least once every three
months. Check all exhaust system pipes, mufflers,
clamps, etc. for condition, tightness, leaks, security,
damage.
4.5.8 CHECK FAN BELT
• Inspect fan belts every three months. Replace any
damaged, deteriorated, worn or otherwise defec-
tive belt.
• Check fan belt tension. Thumb pressure, exerted
midway between pulleys, should deflect about 3/8
to 5/8 inch. Adjust belt tension as required.
4.5.9 INSPECT ENGINE GOVERNOR
Visually inspect electronic governor.
DANGER
DANGER: Do not attempt to adjust the gover-
!
nor. Only qualified service facilities should
adjust the governor. Excessively high operat-
ing speeds are dangerous and increase the
risk of personal injury. Low speeds impose a
heavy load on the engine when adequate
engine power is not available and may short-
en engine life. Correct rated frequency and
voltage are supplied only at the proper gov-
erned speed. Some connected electrical load
devices may be damaged by incorrect fre-
quency and/or voltage. Only qualified service
technicians should adjust the governed speed.

Advertisement