11-7. HOW TO CHECK THE COMPONENTS
<Thermistor feature chart>
Low temperature thermistors
• Thermistor <Outdoor pipe> (TH3)
• Thermistor <Outdoor 2-phase pipe> (TH6)
• Thermistor <Outdoor> (TH7)
• Thermistor <Outdoor pipe> (TH33)
Thermistor R0 = 15 k" ± 3%
B constant = 3480 ± 2%
1
R
=15exp{3480(
t
273+t
0: 15 k"
30:
10: 9.6 k"
40:
20: 6.3 k"
25: 5.2 k"
Medium temperature thermistor
• Thermistor <Heatsink> (TH8)
*ZRP35-71V, ZRP100-140Y only
Thermistor R50 = 17 k" ± 2%
B constant = 4150 ± 3%
1
=17exp{4150( 273+t – 323 )}
R
t
0: 180 k"
25:
50 k"
50:
17 k"
70:
8 k"
90:
4 k"
High temperature thermistor
• Thermistor <Discharge> (TH4)
• Thermistor <Comp. surface> (TH32)
Thermistor R120 = 7.465 k" ± 2%
B constant = 4057 ± 2%
1
=7.465exp{4057( 273+t – 393 )}
R
t
20: 250 k"
70:
30: 160 k"
80:
40: 104 k"
90: 17.5 k"
50: 70 k"
100: 13.0 k"
60: 48 k"
110: 9.8 k"
OCH527C
1
)}
273
4.3 k"
3.0 k"
1
1
34 k"
24 k"
50
40
30
20
10
0
-20 -10 0 10 20 30 40 50
Temperature (:)
200
150
100
50
0
25
Temperature (:)
500
400
300
200
100
0
25
Temperature (:)
66
50
75
100
125
50
75
100
120

Advertisement