[6] Charging of Refrigerant

R407C must be in a liquid state when charging, because it is a non-azeotropic refrigerant.
For a cylinder with a syphon attached
Cylin-
der
Cylinder color identification
Reasons :
1. R407C is a mixture of 3 refrigerants, each with a different evaporation temperature. Therefore, if the equipment
is
charged with R407C gas, then the refrigerant whose evaporation temperature is closest to the outside temperature
is
charged first while the rest of refrigerants remain in the cylinder.
Note :
• In the case of a cylinder with a syphon, liquid R407C is charged without turning the cylinder up side down. Check the
type of cylinder before charging.

[7] Dryer

1. Replace the dryer when the refrigerant circuit is opened (Ex. Change the compressor, full gas leakage). Be sure to
replace the dryer with a CITY MULTI Series Y (For use with R407C).
If any other product is used, the unit will be damaged.
2. Opening the refrigerant circuit after changing to a new dryer is less than 1 hour. The replacement of the dryer
be the last operation performed.
should
R407C-Gray
R410A-Pink
Valve
Liquid
For a cylinder without a syphon attached
Cylin-
der
Charged with liquid refrigerant
Liquid
-6-
Valve