Mitsubishi Electric CITY MULTI PUHY-P400YEM-A Service Handbook page 154

Hide thumbs Also See for CITY MULTI PUHY-P400YEM-A:
Table of Contents

Advertisement

Check Code
6606
Communications with transmission processor abnormality
6607
No ACK abnormality
6608
No response abnormality
6831
MA communication, No-reception error
6832
MA communication, Synchronization recovery error
6833
MA communication, Transmission/reception handware error
6834
MA communication, Start bit error
7100
Total capacity abnormality
7101
Capacity code abnormality
7102
Connected unit count over
7105
Address setting abnormality
7106
Characteristics setting abnormality
7111
Remote control sensor abnormality
7130
Different indoor model connected abnormality
Intermittent fault check code
Trouble Delay Cope
1202 (1102)
Preliminar
Preliminary heat exchanger gas temperature sensor abnormality (variable capacity unit (TH10a,
1204
TH10b), constant capacity unit (TH10a))
1205
Preliminary liquid pipe temperature sensor abnormality (TH5)
1211 (1111)
Preliminary low pressure saturation abnormality or preliminary low pressure saturation sensor abnormality (TH2)
Preliminary low pressure saturation abnormality or preliminary liquid level sensor upper thermal
1212 (1112)
sensor abnormality (TH4)
Preliminary low pressure saturation abnormality or preliminary liquid level sensor lower thermal
1213 (1113)
sensor abnormality (TH3)
1214
Preliminary THHS sensor/circuit abnormality
1216
Preliminary sub-cool coil outlet thermal sensor abnormality (TH7)
1217
Preliminar
1218
Preliminary sub-cool coil bypass inlet thermal sensor abnormality (TH9a)
1219
Preliminary sub-cool coil bypass inlet thermal sensor abnormality (TH9)
1221
Preliminary ambient temperature thermal sensor abnormality (TH6)
1402 (1302)
Preliminary high pressure abnormality or preliminary pressure sensor abnormality
1600 (1500)
Preliminary
1601
Preliminary lacked refrigerant abnormality
1605 (1505)
Preliminary suction pressure abnormality
1607
CS circuit b
1608
Control valve abnormality
1659 (1559)
Oil balance circuit abnormality
[9]
Preliminary serial transmission abnormality
4300 (0403)
4300 (5301)
[6]
IAC sensor/circuit abnormality
[13]
IAC sensor miss-wiring abnormality
4320 (4220)
Preliminary bus voltage abnormality
4330 (4230)
Preliminary heat sink overheating abnormality
4340 (4240)
Preliminary overload protection
[1]
4350 (4250)
IPM Alarm output/Bus voltage abnormality
[11]
IAC sensor overcurrent abnormality
4360 (4260)
Preliminary cooling fan abnormality
Please refer to ( ) : Check Code. [ ] : Error detail No.
y discharge temperature abnormality or preliminary discharge thermal sensor abnormality (TH1)
y sub-cool coil bypass outlet thermal sensor abnormality (TH8)
overcharged refrigerant abnormality
lock abnormality
-151-
Check Content
Trouble Delay Content

Advertisement

Table of Contents
loading

Table of Contents