11-4-2.Poor Cooling Or Heating; 11-4-3.Excessive Cooling Or Heating - Sanyo SAP-KM97GHS5A Technical & Service Manual

Multi-split system air conditioner
Table of Contents

Advertisement

11-4-2.Poor cooling or heating.

• Check position of remote control unit.
Cool or warm air from air conditioner
reaches position directly.
• Wide and narrow tubes between
indoor unit and outdoor unit are
insulated.
• Measure temperature of suction and
discharge air of air conditioner.
Check for clogging of air filter.
• Fan speed is set to LOW.
• Review cooling load estimate,
if performance of air conditioner is
normal.

11-4-3.Excessive cooling or heating.

• Set temperature is suitable.
• Remote control unit is placed where
it can detect room temperature
properly.
NOTE
YES
NO
YES
Temperature
difference
is small.
Temperature difference between
suction and discharge air is
large enough (approx. 10 deg. or more).
Air filter is clogged.
YES
NO
NO
Change position of remote
control unit.
Insulate both wide and narrow
tubes separately and then
tape together.
Possibility of
gas shortage.
Clean filter.
Set fan speed to either
HIGH or MEDIUM.
Reduce cooling or heating
load or replace the air
conditioner with larger
capacity.
Set temperature to higher or
lower value using temperature
setting buttons of the remote
control unit.
Change position of remote
control unit.
36
Charge refrigerant
gas (R22).

Advertisement

Table of Contents
loading

Table of Contents