Operation Instruction - Gree GMV-224WM/G-U Owner's Manual

Commercial air conditioners
Hide thumbs Also See for GMV-224WM/G-U:
Table of Contents

Advertisement

No.
Debugging item
9
10
Outdoor
unit's
11
parameter
System
12
parameter
13
14
15
Indoor
unit's
parameter
16
Drainage
17
system
18
Other

5 Operation Instruction

For instructions on how to use the air conditioner, please refer to the user manual of wired
controller or remote controller.
Debugging Parameter Reference Value for DC Inverter VRF Unit
Parameter name
Opening of electronic
expansion valve of
heating
Operation frequency of
inverter compressor
IPM module
temperature of inverter
compressor
Drive bus voltage of
inverter compressor
Fan operation
frequency
Inlet tube temperature
of indoor heat
exchanger
Outlet tube temperature
of indoor heat
exchanger
Opening of indoor
electronic expansion
valve
Unit
Reference value
● During cooling operation, the
electronic expansion valve of heating is
3000PLS;
PLS
● During heating operation, the
adjustable range of the opening of
electric expansion valve opening is
720~3000PLS.
Hz
● Change among 20Hz~140Hz
● IPM module temperature is lower than
80℃(176℉). The highest temperature
℃ (℉)
doesn't exceed 95℃(203℉).
● The normal bus voltage is 1.414 times
of the power supply voltage. For
example, if the three-phase power supply
voltage is 460V, then the rectified bus
V
voltage is: 460V×1.414 = 650V. The
normal deviation between the measured
value and the calculated value within
15V.
● Adjust the operation in the range of
0~75Hz according to the system
Hz
pressure adjustment.
● According to the ambient temperature,
the inlet temperature is 1℃(33.8℉) ~7℃
℃ (℉)
(44.6℉) lower than the outlet
temperature for the same indoor unit
under cooling mode.
●The inlet temperature is 10 ~20℃
℃ (℉)
(50~68℉) lower than the outlet
temperature for the same indoor unit
under the heating mode.
● 2000PLS electronic expansion valve:
the opening is adjusted automatically in
the range of 200~2000PLS;
PLS
● 480PLS electronic expansion valve:
the opening is adjusted automatically in
the range of 70~480PLS.
● The indoor unit drains smoothly and
thoroughly, and the condensate water
pipe has no slope water storage; the
outdoor unit can drain water from the
drain pipe without dripping directly from
the unit foundation.
●There is no abnormal noise for the
operation of the compressor, indoor fan
and outdoor fan. The unit is running
normally.
59
GMV DC Inverter VRF
Remark