Honeywell Ex-Or MLS2500D Installation And Commissioning Instructions
Honeywell Ex-Or MLS2500D Installation And Commissioning Instructions

Honeywell Ex-Or MLS2500D Installation And Commissioning Instructions

Advertisement

Quick Links

MLS2500D / MLS2500DF
MLS2500DWL* / MLS2500DWLF*
MLS2500DALI / ML2500DALIF
MLS2500DALIWL* / MLS2500DALIWLF*
Digital Mid Range Series Detector
*with Wireless OneSwitch facility
MLS2500D(WL)
MLS2500D(WL)F
MLS2500DALI(WL)
MLS2500DALI(WL)F
Installation and Commissioning
Instructions
Note: QuickSet Pro required for commissioning

Advertisement

loading

Summary of Contents for Honeywell Ex-Or MLS2500D

  • Page 1 MLS2500D / MLS2500DF MLS2500DWL* / MLS2500DWLF* MLS2500DALI / ML2500DALIF MLS2500DALIWL* / MLS2500DALIWLF* Digital Mid Range Series Detector *with Wireless OneSwitch facility MLS2500D(WL) MLS2500D(WL)F MLS2500DALI(WL) MLS2500DALI(WL)F Installation and Commissioning Instructions Note: QuickSet Pro required for commissioning...
  • Page 2 Digital Mid Range Series Detector Fixing Only suitably qualified personnel should install this equipment. 1. This is an extremely sensitive movement detector; it is essential therefore that it be installed on a rigid surface that will not itself be subject to any movement or vibration. 2.
  • Page 3 Electrical Connections Detectors should be connected in accordance with the diagram below. Digital Mid Range Detectors are designed to control up to 25 DSI or DALI ballasts, a switched load of up to 10 Amps or a combination of the two. When controlling DSI or DALI ballasts the ballast types must not be mixed.
  • Page 4 Commissioning The units are supplied with the factory default settings, shown below, which render commissioning, apart from zoning, unnecessary in many applications. To allocate to zone(s), effected via the MLS Bus signals, and make use of the programmable settings, an infrared commissioning tool (QuickSet Pro) is required. A ten-second time delay is selectable to aid commissioning.
  • Page 5 Photocell Control i) Regulating Photocell Regulating photocell control tries to maintain a constant level of total illumination in the space controlled by dimming and brightening the controlled luminaires to compensate for changes in illumination from other sources. With the photocell configured as DISABLED the Regulating Control module is influenced only by the BRIGHT- OUT setting.
  • Page 6 ii) The Primary Interest is the Switching Control Output With the photocell configured as ACTIVE or PASSIVE:- 1) If the lights are not already on, switch them on manually by pressing ‘UTILITIES / LIGHTSPOT/MLS/LCM / IR-REMOTE / HC5 / Luminaire+ / OK’ (QuickSet Pro) or "+" (HC5A). Fluorescent lights do not reach full output until up to 15 minutes after being switched on, so ensure that the lights are fully warmed up before continuing.
  • Page 7 Important Additional Notes All terminals on this product are provided for final connections. It is not intended that the product be used as a junction box for looping cables. Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as mains with regard to wiring practice.
  • Page 8 IP RATING: 4X OPERATING TEMPERATURE: 0 C to 40 C Contact Ex-Or Technical Helpline on 01942 719229 for guidance on installation and commissioning. Honeywell Ex-Or At the end of their useful life Albery House, Springfield Road, the packaging and product...