(6) Hardware specifications
Model
DOP-107CV
Panel type
7" TFT LCD (65535 colors)
Resolution
800 x 480 pixels
Display
Backlight
LED Back Light (half-life under room temperature 25°C > 20,000 hours)
Display range
154.08 x 85.92 mm
Brightness
400 cd / m² (Typ.)
CPU
ARM Cortex-A8 (800 MHz)
Flash ROM
RAM
Touchscreen
4-wire resistive touchscreen > 10,000,000 operated
Buzzer
Multi-tone Frequency (2K – 4K Hz) / 80 dB
Network interface
N/A
USB
1 USB Slave Ver. 2.0; 1 USB Host Ver. 2.0
SD
COM1
RS-232 (supporting flow control)
Serial
communication
COM2
RS-232 (supporting flow control) / RS-485
port
COM3
RS-422 / RS-485
Auxiliary function key
Calendar
Cooling method
Natural cooling
CE / UL (please use shielding network cable and magnetic ring with the
Approvals
filter of 300 ohm / 100 MHz)
Panel waterproof level
IP65 / NEMA4
DC +24V (-15% to +15%) (please use an isolated power supply)
Operation voltage
*2
Supplied by Class 2 or SELV circuit (isolated from MAINS by double insulation)
Leakage current
500 V
for 1 minute (between DC24V terminal and FG terminal)
AC
Power consumption
*2
8.5 W (Max)
*3
Backup battery
3V lithium battery CR2032 × 1
About 3 years or more at 25°C
Backup battery life
(subject to operation temperature and condition)
Operation temperature
0°C to 50°C (32°F to 122°F)
Storage temperature
-20°C to +60°C (-4°F to 140°F)
10% to 90% RH [0°C - 40°C], 10% to 55% RH [41°C - 50°C];
Operating environment
pollution degree: 2
Conforms to IEC61131-2: continuous vibration 5 Hz - 8.3 Hz with
Vibration resistance
amplitude 3.5 mm; 8.3 Hz - 150 Hz with amplitude 1G
Conforms to IEC60068-2-27:
Shock resistance
11 ms, 15 G Peak, in X, Y, Z directions each for 6 times
Dimension
215 x 161 x 50
(W) x (H) x (D) mm
Mounting dimension
196.9 x 142.9
(W) x (H) mm
Weight
Approx. 970 g
Note:
1. The half-life of the backlight is defined as the maximum luminance being reduced by 50% when the
maximum drive current is supplied to the HMI. The life of LED backlight shown here is estimated at the
room temperature of 25°C with ambient humidity.
2. The withstand voltage of the isolated power circuit is 1500V peak for 1 minute.
3. The HMI power consumption is the power consumed when the HMI is not connecting with other
peripheral devices. To ensure normal operation of the HMI, the recommended capacity of the power
supply is 1.5 to 2 times of the specified power consumption.
4. Isolated power supply is recommended.
5. For the DOPSoft programming software of the DOP-100 series and the user manual, you can
download them at http://www.delta.com.tw/ia.
6. DOP-100 series can be used with other industrial automation equipment. Please read through this
sheet carefully and install the product according to the instructions to avoid danger.
DOP-107EV
*1
256 Mbytes
256 Mbytes
1 Port, 10 / 100 Mbps auto detection
*2
(built-in isolated circuit)
N/A
*2
*2
*2
N/A
Built-in
8.76 W (Max)
*3

Advertisement

loading

This manual is also suitable for:

Dop-107evDop-107cv