Daikin Altherma EHVH/X11+16S18CB Installer's Reference Manual page 64

Low temperature split
Table of Contents

Advertisement

8 Configuration
T
Heat pump ON temperature (T
HP ON
T
Domestic hot water temperature
DHW
T
User set point temperature (as set on the user interface)
U
t
Time
Example: setpoint (T
)≤maximum heat pump temperature–[6‑01]
U
(T
–[6‑01])
HP MAX
T
DHW
T
50
HP MAX
T
=T
45
U
HP OFF
[6-00]
T
43
HP ON
40
30
20
HP
10
5
HP
Heat pump. If heating up time by the heat pump takes too
long, auxiliary heating by the booster heater can take place
T
Maximum heat pump temperature at sensor in domestic
HP MAX
hot water tank
T
Heat pump OFF temperature (T
HP OFF
T
Heat pump ON temperature (T
HP ON
T
Domestic hot water temperature
DHW
T
User set point temperature (as set on the user interface)
U
t
Time
INFORMATION
The maximum heat pump temperature depends on the
ambient temperature. For more information, see the
operation range.
Timers for simultaneous request space and domestic hot water
operation
#
Code
N/A
[8-00]
Do not change. (default: 1)
N/A
[8-01]
Maximum running time for domestic hot
water operation. Domestic hot water
heating stops even when the target
domestic hot water temperature is NOT
reached. The actual maximum running
time also depends on setting [8-04].
▪ When
thermostat control: This preset value is
only taken into account if there is a
request for space heating or cooling. If
there is NO request for space heating/
cooling, the tank is heated until the
setpoint has been reached.
▪ When
thermostat control: This preset value is
always taken into account.
Range: 5~95 minutes (default: 30)
N/A
[8-02]
Anti-recycling time.
Minimum time between two cycles for
domestic hot water. The actual anti-
recycling time also depends on setting
[8-04].
Range: 0~10 hours (default: 3) (step: 0.5
hour) (only for EHBH/X).
Range: 0~10 hours (default: 0.5) (step:
0.5 hour) (only for EHVH/X).
Remark: The minimum time is 1/2 hour
even when the selected value is 0.
Installer reference guide
64
−[6-00])
HP OFF
t
−[6-01])
HP MAX
−[6-00])
HP OFF
Description
system
layout
=
Room
system
layout
Room
#
Code
N/A
[8-03]
Booster heater delay timer.
Only for EKHW
Start-up delay time for the booster heater
when domestic hot water mode is active.
▪ When domestic hot water mode is
NOT
20 minutes.
▪ The delay time starts from booster
heater ON temperature.
▪ By adapting the booster heater delay
time versus the maximum running
time, you can find an optimal balance
between the energy efficiency and the
heat up time.
▪ If the booster heater delay time is set
too high, it might take a long time
before the domestic hot water reaches
its set temperature.
▪ The setting [8-03] is only meaningful if
setting [4-03]=1. Setting [4-03]=0/2/3/4
limits the booster heater automatically
in relation to heat pump operation time
in domestic water heating mode.
▪ Make sure that [8-03] is always in
relation with the maximum running
time [8-01].
Range: 20~95 minutes (default: 50).
N/A
[8-04]
Additional running time for the maximum
running time depending on the outdoor
temperature [4-02] or [F-01].
Range: 0~95 minutes (default: 95).
[8-02]: Anti-recycling time
1
0
1
0
[8-00]
[8-01]
[8-02]
1
Heat pump domestic water heating mode (1=active, 0=not
active)
2
Hot water request for heat pump (1=request, 0=no request)
t
Time
[8-03]: Booster heater delay timer
ERHQ+ERLQ011~016 + EHVH/X11+16S18+26CB
Description
active,
the
delay
time
t
Daikin Altherma – Low temperature split
4P384975-1C – 2018.02
is

Advertisement

Table of Contents
loading

Table of Contents