■ FUNCTIONAL BLOCK: fbCMP[0...7]
nv 60
...nv 67
nv 68
...nv 75
• Network Variables
TYPE
NETWORK
{ Range }
VARIABLE
{ Default }
{SNVT_switch}
nviCMPIn1
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
{SNVT_switch}
nviCMPIn2
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
{SNVT_switch}
nvoCMPOut
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
• Configuration Properties
CONFIGURATION
NETWORK
PROPERTY
VARIABLE
SCPTtimeout
----
fbCMP[0...7] (Object ID : 25...32)
Network Variables
nviCMPIn1
SNVT_switch
nviCMPIn2
SNVT_switch
Configuration Properties
fbCMP[ ] :
SCPTtimeout
Delay time before the nvoCMPOut when the
nviCMPIn1 and nviCMPIn2 are deviated.
EXPLANATIONS
Connects to the network variable to be compared.
Connects to the network variable to be compared.
nviCMPIn1 and nviCMPIn2 are compared. OFF is output when both val-
ues are equivalent, ON or 'Invalid' is output when they are not.
ON is output when nviCMPIn1 status change caused the discrepancy.
'Invalid' is output when nviCMPIn2 status change caused it.
OFF is output when nviCMPIn1 and/or nviCMPIn2 is 'Invalid,' regardless
of the values of both.
TYPE
{ Range }
{ Default }
{SNVT_time_sec}
{0.1...60.0}
{5.0}
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
nvoCMPOut
nv 76
...nv 83
SNVT_switch
EXPLANATIONS
Delay time before ON or 'Invalid' is output when a discrep-
ancy occurs between nviCMPIn1 and nviCMPIn2.
OFF is immediately output when nviCMPIn1 and nviC-
MPIn2 states match, regardless of this setting.