M-system R6D-TS2 Instruction Manual page 4

Thermocouple input module, 2 points (euro terminal)

Advertisement

• How to Connect Wires
Wire
Insert a wire. Confirm that the wire tip hits the bottom and
tighten the screw with a screwdriver.
Confirm that the wire's insulation tube is not caught in the
terminal. (Torque: 0.3 N . m)
Wire
Screwdriver
Screwdriver
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
PC CONFIGURATOR
With configurator software, settings shown below are avail-
able.
Refer to the software manual of R6CON for detailed opera-
tion.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER
AVAILABLE RANGE
Sensor type
K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)
R
S
C (WRe 5-26)
N
U
L
P (Platinel II)
(PR)
Lower range value
Depends on sensor type 0.00 (degC)
Upper range value
Depends on sensor type 0.00 (degC)
Fine zero adjustment
-320.00 to +320.00 (%)
Fine gain adjustment -3.2000 to +3.2000
Scaled range Zero
-32000 to +32000
Scaled range Span
-32000 to +32000
Burnout
Upscale, Downscale
■ CHANNEL BATCH SETTING
PARAMETER
AVAILABLE RANGE
Loss of internal bus
0.0 – 99.9 (sec.)
communication detec-
tion time
Conversion rate
250, 500 (msec.)
Temperature unit
degC, degF, K
CJC
ON, OFF
Limit
-15 to +115%
Scaled range Zero / Span
R6D-TS2
DEFAULT SETTING
K (CA)
0.00 (%)
1.0000
0
10000
Upscale
DEFAULT SETTING
1.0 (sec.)
500 (msec.)
degC
ON
-15 to +115%
EM-7781-BG Rev.3 P. 4 / 4