 Outputs
AC230V N=Neutral Open, Close=mixture
Mixing valve
direction
Operating time: 30s~120s
Pool pump
AC230V
Solar pump
AC230V
Zone pump
AC230V
 Thermistor inputs
Zone room
PAW-A2W-TSRT
sensor
Buffer tank
PAW-A2W-TSBU
sensor
Pool water
PAW-A2W-TSHC
sensor
Zone water
PAW-A2W-TSHC
sensor
Solar sensor PAW-A2W-TSSO
12.3.1.3
Recommended External Device
Specification
This section explains about the external devices
(optional) recommended by Panasonic. Please
always ensure to use the correct external device
during system installation.
For optional sensor.
1
Buffer tank sensor: PAW-A2W-TSBU
Use for measurement of the buffer tank
temperature.
Insert the sensor into the sensor pocket and
paste it on the buffer tank surface.
Dimensions (mm)
blue
brown
2
Zone water sensor: PAW-A2W-TSHC
Use to detect the water temperature of the
control zone.
Mount it on the water piping by using the
stainless steel metal strap and contact paste
(both are included).
Dimensions (mm)
35
Ø6
black
40
93
70
3
Outdoor sensor: PAW-A2W-TSOD
If the installation location of the outdoor unit is
exposed to direct sunlight, the outdoor air
temperature sensor will be unable to measure
the actual outdoor ambient temperature
correctly.
In this case, optional outdoor temperature
sensor can be fixed at a suitable location to
more accurately measure ambient
temperature.
Dimensions (mm)
46
4
Room sensor: PAW-A2W-TSRT
Install the room temperature sensor to the
room which requires room temperature
control.
5
Solar sensor: PAW-A2W-TSSO
Use for measurement of the solar panel
temperature.
Insert the sensor into the sensor pocket and
paste it on the solar panel surface.
67
70
93
Dimensions (mm)
30
86
86
Dimensions (mm)
blue
black
brown
40
60
Ø6