13.7.2
External Heater Control at Tank Side
Heating operation condition:
Tank set temperature +
[0°C]
Tank heater Turn On condition:
1
External Heater selected for Tank heater by remote controller.
2
Tank Heater select ON by user.
3
Tank mode operation ON (Tank mode, Heat + Tank, or Cool + Tank).
4
After TANK HEATER DELAY TIMER fulfill during heat pump startup time in tank mode, or during switching
from heating heat-up interval to tank heat + up interval in heat + tank mode.
5
Tank temperature < tank set temperature +[Remote controller Set Tank Re-heat Temp] + [-1°C].
6
20 minutes since previous heater off.
* TANK HEATER DELAY TIMER is clear when tank heat-up interval end.
Tank heater Turn Off condition:
1
Tank temperature > tank set temperature + [0°C] for continuous 15 seconds.
2
When BOOSTER HEATER DELAY TIMER start count after switch from heating heat-up interval to tank heat-
up interval.
3
Tank Heater select OFF by user.
4
Tank Mode Operation OFF.
Heater OFF
Tank set temperature +
Tank Re-Heat Temp. + [ -1°C]
Heater ON
101