Part 12 - Shutdown; Shutdown Procedure; Vacation Procedure; Failure To Operate - Westinghouse WBR080 Series Installation, Start-Up And Maintenance Instructions

Gas fired boiler
Hide thumbs Also See for WBR080 Series:
Table of Contents

Advertisement

NOTE: The boiler will automatically exit test mode after 20 minutes of operation.
Fan Speed
Carbon Monoxide PPM
Carbon Dioxide (CO
)
2
Table 27
MODEL
055
080
110
155
199
285
399
Table 28
PART 12 – SHUTDOWN
A. SHUTDOWN PROCEDURE
If the burner is not operating, disconnect the electrical supply.
If the burner is operating, lower the set point value to 70
blower to stop, so all latent combustion gases are purged from the system. This should take a maximum of 40 to 90 seconds.
B. VACATION PROCEDURE
If there is danger of freezing, change the set point to 70

"Shutdown Procedure".

C. FAILURE TO OPERATE
Should the burner fail to light, the control will perform two more ignition trials prior to entering a lockout state. Note that each
subsequent ignition trial will not occur immediately. After a failed ignition trial, the blower must run for approximately 10 seconds to
purge the system. Therefore, a time period of approximately 40 to 90 seconds will expire between each ignition trial.
If the burner lights during any one of these three ignition trails, normal operation will resume. If the burner lights, but goes off in about 4
seconds, check the polarity of the wiring. See electrical connection section.
If the burner does not light after the third ignition trial, the control will enter a lockout state. This lockout state indicates that a problem
exists with the boiler, the controls, or the gas supply. Under such circumstances, a qualified service technician should be contacted
immediately to properly service the boiler and correct the problem. If a technician is not available, depressing and holding the RESET
button for more than 1 second will remove the lockout state so additional trials for ignition can be performed. The unit will try to re-light
once every 6 minutes.
COMBUSTION SETTINGS ON ALL MODELS
Natural Gas
Low
Ignition
5 – 50
60 - 100
8 - 10%
8 ½ - 10 ½%
FAN SPEEDS
IGNITION
3800
3800
3800
4100
3800
4600
4200
o
F and wait for the burner to shut off. Continue to wait for the combustion
o
F. DO NOT turn off electrical power. If there is no danger of freezing, follow
SERVICE
PUMP ON
High
Low
5 – 50
< 150
8 ½ - 10 ½%
MIN
1650
1850
1850
1850
1750
1800
1900
RUN
3400 RPM
Propane LP
Ignition
60 - 100
< 150
9 - 10 ½%
9 ½ - 11%
MAX
4050
5000
6050
5400
6050
6050
6950
WHL-016 REV. 12.18.14
73
4:49P
High