Frigidaire FFHP093WS2 Installation Manual page 22

Table of Contents

Advertisement

5. Pipe length and refrigerant amount for multi split type air conditioner.
(see tabel 2.3)
Connective pipe
Cooling capacity
length (Lx)
(BTU/h)
26000
34400
Caution in handling the packed valve integrated in the
outlets of outdoor unit.
1. Operation of opening packed valve: Open the valve stem until it hits against
the stopper. Do not try to open it further.
2. Operation of closing packed valve: Securely tighten the valve stem with a
special tool. Then securely tighten the valve stem cap with a spanner or the
like. Refer to the table on page 17 for valve cap tightening torque.
Note: There is a charging port integrated in the low side outlet, but not in the
high side outlet. The low side outlet is shown in the sketch map below.
Outdoor unit
A
B
Packed valve
Purging the system
21
Max connective pipe
total length (H1)
197'
25'~66'
(x=1, 2, 3)
(H1=L1+L2+...+Lx, x≤3)
25'~82'
246'
(H1=L1+L2+...+Lx, x≤5)
(x=1, 2, 3, 4, 5)
Outdoor unit
L1
a
Refrigerant
Indoor unit
Gas
Half union
Table 2.3
Max height
difference (H2)
50'
Use vacuum pump.
50'
Use vacuum pump.
L2
L3
b
c
Indoor unit
Valve body
C
D
Additional amount of
Air purging
refrigerant to be charged
R410a: 0.22ozs/ft (Pipe length-82')
R410a: 0.22ozs/ft (Pipe length-131')
L4
L5
d
e
Flare nut
Charge port
Valve stem
Stopper
Lx
Cap