Other Component Specifications - Technibel Climatisation GR8F98R5IAA Technical Data & Service Manual

Table of Contents

Advertisement

2-3 Other Component Specifications

GR8F98R5IAA
GR8F128R5IAA
4-way Valve (20S)
Coil rating
Coil resistance
Electronic Expansion Valve
Coil rating
Coil resistance / phase
Defrost Valve
Coil rating
Coil resistance
Thermistor (coil sensor)
Resistance
Thermistor (compressor discharge sensor)
Resistance
Thermistor (inlet air sensor)
Resistance
Crank case heater
Resistance
Base heater
Resistance
Ω (at 20°C)
Ω (at 20°C)
Ω (at 20°C)
kΩ
kΩ
kΩ
Ω (at 20°C)
Ω (at 20°C)
9
SQ-136 (Coil)
SHF-4H-23U (Valve)
AC 220/240 V, 50 Hz
1440 ± 5%
ZCAM-MD12EX(Coil)
DC 12 V
46 ± 4%
FQ-235-RK (Coil)
AC 220/240 V - 50 Hz
1273 ± 10%
NTC-THERMISTOR
10 at 25 °C
NTC-THERMISTOR
10 at 25 °C
NTC-THERMISTOR
10 at 25 °C
30 W RESISTANCE
1760 ± 10%
FLEXELEC CSC2
700 ± 10%
DATA SUBJECT TO CHANGE WITHOUT NOTICE
ZCAM-BD15EX (Valve)
FDF6A-049-RK (Valve)