Use the market brass pipe
Be sure to use the same insulating materials when you buy the brass pipe (more than 9mm thick).
2. Locate The Pipes
Drill a hole in the wall (suitable just for the size of the wall conduit, 53, 71 series diameter is
and 120,105,140 series diameter is
conduit and its cover.
Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which
will cause water leakage by condensation.
Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe alloc-
ation to do no damage to the tubing.
3. Connect the pipes.
4. Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connec-
ting the indoor unit with the outdoor unit in fluent flow.
5. Be sure of no leakage by checking it with leak detector or soap water.
6. Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating
sheath (fittings), and bind it well with the tapes to prevent leakage.
Flaring
Lean
90
Chart 22
Fasten the nuts
Put the connecting tubing at the proper position,
wrench the nuts with hands, then fasten it with a
wrench.( Refer to Chart24)
Necessary Refrigerant Stow Capacity
LENGTH(L)
Less than 8m (one-way)
Added Refrigerant When Over 8m(one-way)
Please record and reserve well the refrigerant stow capacity of your air conditioner for later maintenance.
Ф
105 in general), then set on the fittings such as the wall
crude
burr
Chart 23
Chart 24
Capacity
1. Cut a pipe with a pipe cutter.
2. Insert a flare nut into a pipe and flare
the pipe.
Outside-diameter
(mm)
6.35
9.53
12.7
16
19
CAUTIONS
Too large torque will harm the bellmouthing
and too small will cause leakage. Please
determine the torque according to Table 2.
Tubing Size
φ
6.35
φ9.53
φ12.7
φ16 6
φ19 9
18000-24000Btu/h 30000-48000Btu/h
65g (L-8)m
Table 3
10
A(mm)
Max
8.3
12.4
15.8
19.0
23.3
Torque
.
1420~1720 N cm
(144~176kgf cm)
.
3270~3990 N cm
(333~407kgf cm)
.
4950~6030 N cm
(504~616kgf cm)
.
6180~7540 N cm
(630~770kgf cm)
.
9720~11860 N cm
(990~1210kgf cm)
Table 2
×
Ф
90mm,
Min
8.3
12.0
15.4
18.6
22.9
.
.
.
.
.
(kg)