SELF-DIAGNOSIS LIGHTING MODE
MODEL RAC-E10H2
CUT THE POWER 
SOURCE AND WAIT 
MORE THAN 10 
MINUTES BEFORE 
SERVICE WORK. 
DO NOT TOUCH THE 
OTHER COMPONENTS 
WHEN OPERATING THE 
SERVICE SWITCH. 
PROCEDURE OF REFRIGERANT PUMP 
DOWN OR INDEPENDENT OPERATION 
OF OUTDOOR UNIT. 
1. CUT OFF THE POWER SOURCE 
   ONCE THEN ON AGAIN. 
2. WAIT 1 MINUTE AT LEAST. 
3. PRESS THE SERVICE SWITCH 
   (WHICH IS ON THE PWB) MORE 
   THAN 1 SECOND. 
SERVICE OPERATION WILL BE 
STARTED. 
TO STOP THIS OPERATION, PRESS 
THE SERVICE SWITCH AGAIN (MORE 
THAN 1 SECOND). 
TO RESUME TO NORMAL OPERATION, 
CUT THE POWER SOURCE ONCE THEN 
ON AGAIN. 
IN ORDER TO PROTECT THE DAMAGE 
OF COMPRESSOR, DO NOT OPERATE 
MORE THAN 5 MINUTES WITH 
SERVICE VALVE CLOSE. 
LD303
MAIN P.W.B.
LD302
LD301
IPM
HIC
DANGER 
(DC350V) 
SERVICE  OPERATION 
SELF−DIAGNOSIS LIGHTING MODE 
L 
L 
D 
D 
SELF−DIA− 
3 
3 
0 
0 
1 
2 
[1]DURING OPERATION 
NORMAL 
OPERATION 
OVERLOAD 
   (1) 
OVERLOAD 
   (2) 
OVERLOAD 
   (3) 
[2]DURING STOP 
NORMAL 
STOP 
RESET 
STOP 
1TIME 
PEAK 
CURRENT 
CUT 
2TIMES 
ABNORMAL 
LOW SPEED 
ROTATION 
3TIMES 
SWITCHING 
FAILURE 
4TIMES 
OVERLOAD 
LOWER 
LIMIT CUT 
5TIMES 
OH THERMISTOR 
TEMP.RISE 
6TIMES 
THERMISTOR 
ABNORMAL 
7TIMES 
ACCELERATION 
FAILURE 
8TIMES 
COMMUNICA− 
TIONS ERROR 
9TIMES 
ABNORMAL 
POWER 
10TIMES 
SOURCE 
FAN LOCK 
ERROR 
12TIMES 
EEPROM 
READ 
13TIMES 
ERROR 
※EXAMPLE OF 
BLINKING (5 TIMES) 
VICE SWITCH
- 76
-
:LIGHT 
 
DETAILS 
MAIN CHECK POINT 
 LD303(RED)LIGHTS.  
COMPRESSOR 
NOT MALFUNCTION 
OPERATION 
(1) 
(2) 
SET 
VALUE 
(3) 
THIS SHOWS AN 
TIME 
OVERLOAD PROTECTION 
THE ROTATION SPEED IS 
STATUS. 
AUTOMATICALLY CONT− 
ROLLED TO PROTECT THE 
COMPRESSOR IN THE 
NOT MALFUNCTION. 
OVERLOAD CONDITION. 
 LD303(RED)GOES OFF.   
STOPPED BY THERMOSTAT 
NOT MALFUNCTION. 
OR CONTROLLER. 
MICROPROCESSOR WAS 
REBOOTED. (IT IS NORMAL 
MAIN P.W.B. 
1 
WHEN POWER SW HAS BEEN 
TURNED ON) 
COMPRESSOR PEAK 
MAIN P.W.B. 
1 
CURRENT WAS BEYOND 
COMPRESSOR 
2 
MAXIMUM LIMIT. 
LOST THE COMPRESSOR 
MAIN P.W.B. 
1 
ROTOR POSITION. 
COMPRESSOR 
2 
SWITCHING FROM LOW 
MAIN P.W.B. 
1 
FREQUENCY SYNC START 
COMPRESSOR 
TO POSITION DETECTION 
2 
OPERATION FAILURE. 
 OUTDOOR UNIT IS EXPOSED TO DIRECT 
 OUTDOOR UNIT IS EXPOSED TO DIRECT 
 OUTDOOR UNIT IS EXPOSED TO DIRECT 
OVERLOAD PROTECTION 
1 
1 
FUNCTION IS REQUESTING 
 SUNLIGHT OR ITS AIRFLOW BLOCKED. 
FAN MOTOR  
LOWER SPEED THAN MINIMUM 
2 
THE VOLTAGE IS EXTREMELY LOW. 
SPEED OF COMPRESSOR.
4 
LEAK OF REFRIGERANT  
COMPRESSOR OVERHEAT 
1 
OH THERMISTOR CIRCUIT 
WAS DETECTED BY 
3 
  (MAIN P.W.B.) 
OH THERMISTOR. 
THERMISTOR  
ABNORMAL THERMISTOR 
1 
 OF THERMISTOR DEFECTIVE 
VALUE (OPEN OR SHORT) 
WAS DETECTED. 
THERMISTOR CIRCUIT 
3 
COMPRESSOR WAS NOT 
LEAK OF REFRIGERANT 
1 
ACCELERATED MORE THAN 
COMPRESSOR 
2 
MINIMUM SPEED. 
CABLE IS WRONG CONNECTED 
COMMUNICATIONS BETWEEN 
1 
CABLE IS 0PEN 
2 
INDOOR UNIT AND OUTDOOR 
 CIRCUIT OF BETWEEN INDOOR 
UNIT ARE INTERRUPTED 
 UNIT AND OUTDOOR UNIT 
ABNORMAL POWER SOURCE 
ABNORMAL POWER SOURCE 
1 
CABLE IS WRONG CONNECTED 
2 
WAS DETECTED 
MAIN P.W.B. 
3 
OUTDOOR FAN RPM IS 
FAN MOTOR 
1 
NOT ROTATE AS INTENDED 
FAN MOTOR CIRCUIT 
2 
RPM 
MICROCOMPUTER CANNOT 
MAIN P.W.B. 
1 
READ THE DATA IN EEPROM. 
2SEC
:BLINK 
:OFF
MAIN P.W.B.
3 
COMPRESSOR 
2 
CONNECTION 
2 
INTERFACE
3 
 ・・LIGHTS FOR 0.25 
 ・・LIGHTS FOR 0.25 
   SEC AT INTERVAL 
   SEC AT INTERVAL 
   OF 0.25 SEC. 