6-6. Electric expansion valve control circuit
Main P.W.B.
Electric
expansion
valve
C 4 0 1
C N 1 5
WHT
XA− 6 P
Electric expansion valve is driven by B-12V. Opening of the valve is controlled by feeding power to 1
or 2 phases of the 4-phase coil to switch the polarity of the coil.
The relation between the conducting phase switching direction and open/close direction is as shown
below. When the power is turned on, approx. 0.9 V is applied to CN15 pins 1 to 4 ; when no power
is supplied, approx. 12 V is applied. When the power is reset, expansion valve performs initial
operation for 5 to 10 seconds.During initial operation, measure pins 1 to 4 of CN15 using
multimeter: If no change is found around 0.9 V or 12V, expansion valve or microcomputer is
defective.
Fig. 6-15 shows logic waveform during the operation of expansion valve.
Co n n e c t o r    
P i n  No .
B − 1 2 V
R 4 0 4
1 5
1 4
1 0 0
1 1
1 2
1 3
Ⅰ C 6
B − 0 V
CN 15
Lead
Pin No.
wire
1
O N
White
O F F
Yellow
O F F
Orange
O F F
Blue
O p e r at i o n   m o d e
  1 → 2 → 3 → 4 → 5 → 6 → 7 → 8   VA LV E C LO S E
  8 → 7 → 6 → 5 → 4 → 3 → 2 → 1   VA LV E O P EN
50m s .
+ 5 V
R 4 0 3
R 4 0 7
P Q 4 0 1
R 4 0 8
P Q 4 0 2
R 4 0 9
P Q 4 0 3
R 4 1 0
P Q 4 0 4
Fig. 6-14
Table 6-4
Drive status
2
3
4
5
O N
O FF
O FF
OFF
O N
ON
O N
O FF
O F F
O FF
O N
ON
O F F
OF F
O FF
O FF
7 5 m s .
2 0 0 m s .
Fig. 6-15
- 64 -
H Ⅰ C
Q 4 0 1
1 6
Q 4 0 2
1 5
Q 4 0 3
R 2 2 9 9 3
R 2 9 4
Q 4 0 4
1 4
R 2 9 5
1 3
R 2 9 6
6
7
8
O FF
O FF
O N
OFF
O FF
OFF
O N
O FF
O FF
O N
O N
ON
1 2 V
0 . 9 V
Microcomputer
5 8 8
 Valve 4
5 7
 Valve 3
5 6
 Valve 2
5 5 5
 Valve 1