1. Introduction
TOSVERT VF-S15 is equipped with shock monitoring function.
In case output current or torque exceeds or lowers the set level for a certain amount of time, the inverter
outputs the alarm signal from output terminals or trips (inverter stops). Temporary change in current or
torque can be eliminated from detecting conditions.
Shock monitoring function enables monitoring the load side and protecting the equipments in case of load
abnormality including the detection of excessive loading of conveyors and breakage of conveyor belt.

2. Shock monitoring function

When output current or torque exceeds or lowers the set level for a certain amount of time, shock
monitoring function outputs alarm signal from the output terminals or the inverter trips.
Over-torque trip/ alarm and small current trip/alarm have similarly functions as the shock monitoring
functions. The difference is as described below;
Main parameters
Subject of detection:
torque/ output current
Detection method
Action at detection
Detection level
Detection time
Detecting conditions
* Temporary change in output current or torque at start-up or acceleration/ deceleration can be eliminated
from detecting conditions.
Shock monitoring function
f590
(Shock monitoring)
Torque detection or output
current detection are
selectable
Over-current/ torque or
Low-current/ torque are
selectable
Trip or alarm are selectable
0-250(%)
0-10.0 (s)
-Detection waiting time
can be set at start-up
-Always detecting or
during operation except
acceleration/deceleration
are selectable *
2
Over-torque trip/ alarm
f615
(Over-torque trip/
alarm selection)
Torque detection
Over-torque
1-250 (%)
0-10.0 (s)
Always detecting
E6581875
Small current trip/ alarm
f610
(Small current trip/
alarm selection)
Output current detection
Low-current
0-150 (%)
0-255 (s)
Always detecting