LEGRAND Wattstopper LMPX-100 Installation Instructions
LEGRAND Wattstopper LMPX-100 Installation Instructions

LEGRAND Wattstopper LMPX-100 Installation Instructions

Dlm-occupancy sensor pir corner mount with dense lens

Advertisement

No: 24779 – 09/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPX-100
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
LMPX-100-U is BAA and TAA compliant (Product produced in the U.S.)
This unit is pre-set for Plug n' Go™ operation, adjustment is
optional.
For full operational details, adjustment and more features of the product, see the
DLM System Installation Guide provided with Wattstopper room controllers, and
also available at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable regulations, local and
NEC codes. Wire connections shall be rated suitable for the wire size (lead and
building wiring) employed.
For Class 2 DLM devices and device wiring: To be connected to a Class 2 power
source only. Do not reclassify and install as Class 1, or Power and Lighting Wiring.
Sensor
Coverages shown are maximum and represent half-step walking motion.

SENSOR PLACEMENT

30'
30'

COVERAGE PATTERN

10'
Side view
0 7' 15' 25'
Wattstopper
DLM - Occupancy Sensor PIR Corner Mount With Dense Lens
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltage .............................................................................. 24VDC
Current Consumption .............................................................7mA
Power Supply ................................Wattstopper Room Controllers
Connection to the DLM Local Network ........................ RJ-45 plug
DLM Local Network characteristics when using LMRC-11x/2xx
room controllers:
Low voltage power provided over Cat 5e cable (LMRJ);
max current 800mA. Supports up to 64 load addresses,
48 communicating devices including up to 4 LMRC-10x
series and/or LMPL-101 controllers.
Free topology up to 1,000' max.
Environment ................................................. For Indoor Use Only
Operating Temperature .................32° to 131°F (0° to 55°C)
Storage Temperature ...................23° to 176°F (-5° to 80°C)
Relative Humidity .......................5 to 95% (non condensing)
Patent Pending
Ceiling
Sensor
Top view
45'
®

SPECIFICATIONS

45'

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Wattstopper LMPX-100 and is the answer not in the manual?

Questions and answers

Summary of Contents for LEGRAND Wattstopper LMPX-100

  • Page 1 For full operational details, adjustment and more features of the product, see the DLM System Installation Guide provided with Wattstopper room controllers, and Environment ..........For Indoor Use Only also available at www.legrand.us/wattstopper. Operating Temperature ....32° to 131°F (0° to 55°C) Storage Temperature ....23° to 176°F (-5° to 80°C) Installation shall be in accordance with all applicable regulations, local and Relative Humidity .......5 to 95% (non condensing)
  • Page 2 CONNECTIVITY The illustrations below show examples of free-topology wiring. The LMPX-100 communicates to all other Digital Lighting Management devices connected to the low voltage DLM Local Network, regardless of their position on the DLM Local Network. CAUTION: TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.
  • Page 3 FACTORY PRE-SET OPERATION Sensor Parameters T-DELAY Time Delay 20 minutes Passive Infrared Sensitivity Walk-Through Load Parameters Load 1 Loads 2-8 Plug Load or more** MANUAL-ON ON Mode if switch is used. AUTO- AUTO-ON Operation* AUTO-ON if switch is not used. Blink Warning Daylighting NOTE: *Auto-OFF is enabled according to the sensor Time Delay when a sensor is bound to the load, regardless of whether the load...
  • Page 4 No. 24779 – 09/16 rev. 1 © Copyright 2016 Legrand All Rights Reserved. 800.879.8585 © Copyright 2016 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2016 Legrand Todos los derechos reservados.

This manual is also suitable for:

Wattstopper lmpx-100-u

Table of Contents