Input configuration
Parameter
Description
IP 00
TI1: Celsius or Fahrenheit, C = OFF, F = ON
IP 01
TI1: Samples taken for averaging control signal
IP 02
TI1: Calibration
IP 03
TI1: Minimum temperature range
(temperature when output is at its minimum)
IP 04
TI1: Maximum temperature range
(temperature when output is at its maximum)
IP 05
CI1: Light intensity of air quality LED on front
IP 06
CI1: Samples taken for averaging control signal
IP 07
CI1: Calibration
IP 08
CI1: Minimum CO2 range ppm
(CO2 level when output is at its minimum)
IP 09
CI1: Maximum CO2 range ppm
(CO2 level when output is at its maximum)
IP 10
CI1: CO2 level for medium CO2 indication
IP 11
CI1: CO2 level for high CO2 indication
IP 12
CI1: Enable ABC automatic CO2 background calibration
IP 13
CI1: Calibrate CO2 sensor
Note: For normal operation, calibration is not required. Only experts
should calibrate the sensor.
0 = No calibration (default)
1 = Calibrate to gas (0 ppm)
2 = Calibrate to fresh air (400 ppm)
1)
Sample interval: 1 sec.
2)
Changing this parameter affects the control of the air quality LEDs or relay as follows:
Air quality LED
Use of Parameters
Green
IP 08 value ... (IP 10 value + 400) / 2
Green + Orange
(IP 10 value + 400) / 2 ... IP 10 value
Orange
IP 10 value ... (IP 10 value + IP 11 value) / 2
Orange + Red
(IP 10 value + IP 11 value) / 2... IP 11 value
Red
IP 11 value ... IP 09 value
Output configuration
Parameter
Description
OP 00
AO1 (CO2): Configuration of CO2 output signal:
0 = CO2 value
1 = Recorded minimum CO2 value
2 = Recorded maximum CO2 value
OP 01
AO1 (CO2): Minimum limitation of CO2 output signal
OP 02
AO1 (CO2): Maximum limitation of CO2 output signal
OP 03
AO2 (temperature): Configuration of temperature output signal:
0 = Temperature value
1 = Recorded minimum temperature value
2 = Recorded maximum temperature value
OP 04
AO2 (temperature): Minimum limitation of temperature output
signal
3) 4)
OP 05
AO2 (temperature): Maximum limitation of temperature output
signal
3) 4
3)
The Output signal will be scaled according to selected input range, selected limitation of output signal and the output
signal range selected by the jumper.
4)
If the default values are changed, the position of JP2 has no influence and the output signal range defined with the
parameters applies.
IP
=
Input Parameter
OP
=
Output Parameter
CI
=
CO2 Input
TI
=
Temperature Input
AO
=
Analog Output
Doc: 70-00-0794A, V2.7, 20210310
Subject to change without notice
CO2+T
1)
1)
2)
2)
2)
2)
3) 4)
3) 4)
© Vector Controls GmbH, Switzerland
www.vectorcontrols.com
T
EMPERATUR
RANSMITTER
Range
ON, OFF
1...255
-10...10
-40...215 °C
-40...419 °F
-40...215 °C
-40...419 °F
0...10
1...255
-10...10%
0...5000 ppm
0...5000 ppm
0...5000 ppm
0...5000 ppm
ON, OFF
0...2
Range
0...2
0...100 %
0...100 %
0...2
0...100 %
0...100 %
SRC-C1T1
/M
ONITOR
Default
OFF
10
0
-40 °C
-40 °F
60 °C
140 °F
8
10
0
0 ppm
2000 ppm
1000 ppm
1600 ppm
ON
0
Default
0
0 %
100 %
0
0 %
100 %
Page 6-10