Technical Specifications

Power supply
Operating voltage
Power consumption
Connection
Terminal connectors
Sensing method
CO2 measurement
Sampling method
Response time (90%)
Measurement range
Repeatability
Accuracy
Pressure dependence
Accuracy:
Temperature -
0...50°C (32...122°F)
measurement
50...60°C (122...158°F)
Note on accuracy: allow one hour for temperature compensation to stabilize after power up
Signal outputs
Analog outputs
Output signal
Resolution
Maximum load
Relays output
Insulation strength
between relays and system electronics
between neighboring contacts
Operation
Environment
Climatic conditions
Temperature
Humidity
Transport & storage
Climatic conditions
Temperature
Humidity
Mechanical conditions
Standards
Degree of protection
Safety class
Housing materials
Cover
Mounting plate
General
Dimensions (H x W x D)
Weight (including package)
Product testing and certification
Declaration of
Conformity
Doc: 70-00-0794A, V2.7, 20210310
Subject to change without notice
Information on the conformity of our products can be found on our website
www.vectorcontrols.com
on the corresponding product page under "Downloads".
© Vector Controls GmbH, Switzerland
www.vectorcontrols.com
CO2+T
T
EMPERATUR
24 VAC 50/60 Hz ± 10%, 24 VDC ± 10%
SELV to HD 384, class II transformer, 48 VA max.
Max. 2 VA
For wire 0.34...2.5 mm
2
(AWG 24...12)
Non-dispersive infrared (NDIR) waveguide technology
with ABC automatic background calibration algorithm
Diffusion
2 Minutes
0 - 2000 ppm
vol.
± 20 ppm ± 1 % of measured value
± 40 ppm ± 3 % of measured value
+ 1.6 % reading per kPa deviation from normal
pressure, 100 kPa
0.5 °C (1 °F)
1 °C (2 °F)
DC 0...10 V or DC 2...10 V
10 bit, 9.7 mV
Voltage signal: ≥1kΩ
48 VAC, 1 A max., 30 VDC, 1 A max.
500 VAC to EN 60 730-1
500 VAC to EN 60 730-1
To IEC 721-3-3
class 3 K5
0...50° C (32...122° F)
<95% RH non-condensing
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-30...70° C (-22...158° F)
<95% RH non-condensing
class 2M2
IP30 to EN 60 529
III (IEC 60536)
Fire proof ABS plastic
Aluminium
21 x 88 x 88 mm (0.8 x 3.5 x 3.5 in)
129 g (4.6 oz)
SRC-C1T1
/M
RANSMITTER
ONITOR